Outputs on the unit: o1, o2, o3
Only for models with automatic CHIPS control
On terminal block X510, the unit has three signal
interfaces for an output signal. These can be used (for
example) for controlling the central heating or for
transmitting status reports to a BMS.
Caution:
The outputs are dry contacts (relays). Their
maximum load is 24 V / 1 A.
Options and operation
Options and operation depend on the input or output
and on the control panel settings.
2.9.2
Installing the outdoor temperature sensor. Only for
models with automatic CHIPS control
The CHIPS control requires an outdoor temperature in
order to operate correctly. To this end, there are
various possibilities.
Note:
The desired possibility is selected in the
installation guide.
1. A wired outdoor temperature sensor
2. A table giving average temperatures per month
Caution:
The automatic control works less efficiently
without an outdoor temperature sensor.
Note:
If use is made of the table, there is a symbol for
the absence of an outdoor temperature sensor
on the control panel.