38
Daisy chaining multiple units with a single
controller
Note:
Check in 2.7.1 Special points regarding the
controller
to see how many units can be
connected to the controller.
1. Lay the cable between the electronic
compartments of the units to be connected
Feed the cable through the feed-through holes
Fasten the cable to the edge inside the units,
using the cable clips.
Warning:
Do not allow the cable to lie or hang
loosely.
2. Feed the cable into the electronic compartments of
both units.
Fabricate the grommets in the electronic
compartment to measure.
Feed the cable through the wall of the electronic
compartment.
Caution:
Ensure that the grommets fit so tightly around
the cable that they remain watertight.
3. Connect the cable in both units to terminal block
X60
4. Repeat steps 1 to 3 for each unit to be connected.
2.7.3
Connecting an extra controller to the unit
(optional)
The fans have a start-up time of approximately
3 seconds. This can be remedied with an extra
controller which causes the fans to rotate very
slowly if the door is closed.
Note:
The fans also continue rotating slowly at
night. If this is not desired, switch the unit off
at night with the controller that is used for
operating it.
n
w
c
n
1
2