47
Connecting the alarm signal to the unit
For models with automatic control (Auto type)
The alarm signal can be received via an output,
ModBus or another building management system.
Establish the required connection.
For models with basic control (Basic type)
1. Install the alarm cable (not supplied) between the
unit and the appliance on which the alarm signal is
received.
Note:
If the alarm signal is to be connected in series
with several other units: Install the cable to the
unit which is going to serve as the master.
2. Connect the alarm cable to the appliance on which
the alarm signal must be received.
3. Connect the alarm cable in the unit to the TK
clamps on terminal X15 .
Multiple units with a single alarm signal
In a multiple-unit setup, the alarm signal is
connected in series between the units.
Note:
In a setup consisting only of units having a
basic control (Basic type), each unit can also be
connected independently to an alarm signal.
1. Lay the alarm cable between the units.
2. Connect the alarm cable to terminal X15 on the
first unit to which the alarm signal is already
connected (Auto or Basic master):
Remove the jumper
Connect the cable
n
n
3
2