TIP 5000 Unit heaters
Wall- and ceiling-mounted units - The simple solution
Installation instructions
1.57
3. Description
1. Correct and proper use
Kampmann TIP 5000 unit heaters are manufactured in
accordance with state of the art engineering and recognised
safety directives. However, incorrect installation and
commissioning of the units together with improper use of the
units can cause fatal injury, damage to the unit heaters or
damaged to other units or systems!
Kampmann unit heaters are intended only to be used to heat
and ventilate industrial premises, assembly and production
plants, retail premises, sports halls and greenhouses. The units
are fitted with a copper/aluminium heat exchanger and, as such,
can be supplied with LPHW up to a maximum temperature of
120 °C and can operate at a maximum pressure of 16 bars. The
units should not be used for any purpose other than the one
described above. Damage resulting from improper use is the
sole responsibility of the user. Correct and proper use is also
understood as meaning the implementation of the installation
instructions given in this manual.
2. Important safety information
l
These units should be wired and serviced by qualified
electrical technicians in accordance with the Association of
German Electrician's (VDE) or EN standards and recognised
electrical guidelines.
l
Non-observance of these directives and of the detailed
instructions provided in the installation manual may cause
malfunction of the unit, resulting in damage to the unit itself
and possible fatal injury.
l
Incorrect wiring may also result in fatal injury!
l
All parts of the system should be disconnected and isolated
from the mains prior to electrical wiring and service work or
any other work being carried out.
l
The unit can also be damaged by the use of incorrect switches
or inadequate fuses. The Manufacturer's guarantee is
automatically invalidated in these circumstances.
l
The units should only be wired to a circuit in which the live
wires are separated from the mains circuit, with a 3 mm gap
between each contact.
4. Water pipe connections
The flow and return pipework should be connected to the unit
heater as indicated on the unit.
5. Fixing
TIP 5000 unit heaters can be:
l
wall-mounted using wall brackets type 3*044
l
ceiling-mounted using universal 4-point brackets, type 30042
The unit can also be fixed using M8 ceiling rods or similar (by
others). When fixing a unit to the wall or ceiling, a minimum
gap A should be allowed between the fan guard and the wall
or ceiling. If this gap is not observed the performance of the unit
may be impaired and the noise level may increase.
Model/Type
54**36
55**36
56**36
57**36
Height
500
600
700
800
Width
500
600
700
800
Depth
280
280
280
280
Dimensions*
When connecting the flow and return pipework to
the unit heater, ensure that the threaded parts of
the heat exchanger are held rigid with pipe pliers or
similar to prevent them from becoming damaged or
bent.
Type
54*036
55*036
56*036
57*036
Minimum gap
A (mm)
160
180
230
300
Model
4
5
6
7
Minimum gap between units and wall/ceiling
* Dimensions without fan guard and air outlet louvre
1
M8 screw
2
Electrical junction box
3
Flow pipework
4
Return pipework
1
1
1
1
2
3
4
I 097/09/02/0.5 GB
A
A