background image

TIP 5000 Unit heaters

Wall- and ceiling-mounted units - The simple solution

Installation instructions

1.57

3. Description

1. Correct and proper use

Kampmann  TIP  5000  unit  heaters  are  manufactured  in
accordance  with  state  of  the  art  engineering  and  recognised
safety  directives.  However,  incorrect  installation  and
commissioning of the units together with improper use of the
units  can  cause  fatal  injury,  damage  to  the  unit  heaters  or
damaged to other units or systems!
Kampmann unit heaters are intended only to be used to heat
and  ventilate  industrial  premises,  assembly  and  production
plants,  retail  premises,  sports  halls  and  greenhouses.  The  units
are fitted with a copper/aluminium heat exchanger and, as such,
can be supplied with LPHW up to a maximum temperature of
120 °C and can operate at a maximum pressure of 16 bars. The
units  should  not  be  used  for  any  purpose  other  than  the  one
described  above.    Damage  resulting  from  improper  use  is  the
sole  responsibility  of  the  user.    Correct  and  proper  use  is  also
understood as meaning the implementation of the installation
instructions given in this manual.

2. Important safety information

l

These  units  should  be  wired  and  serviced  by  qualified
electrical  technicians  in  accordance  with  the  Association  of
German  Electrician's  (VDE)  or  EN  standards  and  recognised
electrical guidelines. 

l

Non-observance  of  these  directives  and  of  the  detailed
instructions  provided  in  the  installation  manual  may  cause
malfunction of the unit, resulting in damage to the unit itself
and possible fatal injury.

l

Incorrect wiring may also result in fatal injury!

l

All  parts  of  the  system  should  be  disconnected  and  isolated
from the mains prior to electrical wiring and service work or
any other work being carried out.

l

The unit can also be damaged by the use of incorrect switches
or  inadequate  fuses.  The  Manufacturer's  guarantee  is
automatically invalidated in these circumstances.

l

The  units  should  only  be  wired  to  a  circuit  in  which  the  live
wires are separated from the mains circuit, with a 3 mm gap
between each contact.

4. Water pipe connections

The flow and return pipework should be connected to the unit
heater as indicated on the unit. 

5. Fixing

TIP 5000 unit heaters can be:

l

wall-mounted using wall brackets type 3*044

l

ceiling-mounted using universal 4-point brackets, type 30042

The  unit  can  also  be  fixed  using  M8  ceiling  rods  or  similar  (by
others).  When  fixing  a  unit  to  the  wall  or  ceiling,  a  minimum
gap A should be allowed between the fan guard and the wall
or ceiling. If this gap is not observed the performance of the unit
may be impaired and the noise level may increase.

Model/Type

54**36

55**36

56**36

57**36

Height

500

600

700

800

Width

500

600

700

800

Depth

280

280

280

280

Dimensions*

When connecting the flow and return pipework to
the  unit  heater,  ensure  that  the  threaded  parts  of
the heat exchanger are held rigid with pipe pliers or
similar to prevent them from becoming damaged or
bent.

Type

54*036

55*036

56*036

57*036

Minimum gap

A (mm)

160

180

230

300

Model

4

5

6

7

Minimum gap between units and wall/ceiling

* Dimensions without fan guard and air outlet louvre

1

M8 screw

2

Electrical junction box

3

Flow pipework

4

Return pipework

1

1

1

1

2

3

4

I 097/09/02/0.5 GB

A

A

SYSTEMS FOR HEATING · COOLING · VENTILATING

Reviews: