Chapter 4 Software index
4-30
1. RS-485 communication:
(requires RS485 option card)(Option)
1 to 1 control
: PC, PLC or other device can control one
iDrive
on the communication link at
any given time. Each
iDrive
requires that b77 is set between 001~254. Only the
iDrive
with
the correct address will reply to the master with an Acknowledge/Not Acknowledge
message.
1 to many control:
PC, PLC or other device can send a ‘broadcast’ message to all
iDrive’s
on
the communication link by sending to address 000. In this transmission mode all of the
connected
iDrive’s
each receive the same command (regardless of setting b77 on each
iDrive
)
but do not reply to the master.
2. RS-232 communication:
(requires RS232 port device)(Option)
1 to 1 control: PC or PLC or controller controls one inverter (b77 is set to 001~254).
※
Note: a
. The baud rate (b78) and communication format (b79/b80/b81) of PC (or PLC or other
controller) and
iDrive
should be the same.
b
. The
iDrive
will validate any modified parameters after the parameters are modified by
PLC or PC etc.
c
. Communication protocol: refer to EDX communication protocol description.
d
. Parameters b77~b81 cannot be changed in communication mode.
b82
Communication error detection time (s)
b83
Communication error – inverter response
(1) Time-out detection time: 00.0~25.5sec; setting 00.0 sec: disable time-out function.
Default = 00.0sec
*Cannot
be changed in communication mode.
(2) Time-out operation selection:
000 : Deceleration to stop (A05 : Deceleration time 1).
001 : Coast-to-stop.
002 : Deceleration to stop (b01 : Deceleration time 2).
003 : Continue operating (Ignore error).
Default = 000
*Cannot
be changed in communication mode.
See Communication error timing diagram following.