Chapter 4 Software index
4-1
Chapter 4 Programming instructions & Parameter list
4.1 Keypad
4.1.1
Keypad layout
4.1.2
Local and Remote operating modes
Local mode
Run Command
Set
(A00 = 000)
:
Run command only from
RUN / STOP
keys on the keypad.
Frequency command
Set
(A01 = 000):
UP/DOWN keys on keypad control the motor frequency (speed).
Set
(A01 = 001):
only the ‘Freq.Set’ potentiometer (VR) on the keypad can control the motor speed.
Remote mode
Run Command
Set
(A00 = 001)
:
Run command only by digital input to TM2 terminal S1 to S4.
Terminals S1 to S4 can be configured for ‘RUN’ input by setting functions (
b34 to b38 = 000 / 001)
Frequency command
Set
(A01 = 002):
only external speed reference to TM2 terminal 10 (AIN) can control the motor speed.
Note: Switch SW2 and
(b61 = 000 / 001)
must be set for either 0-10V or 4-20mA input.
Tip!
Quick changeover between
LOCAL
and
REMOTE
control modes can be made by
simultaneously pressing the
and the
keys on the keypad.
Modes can be ‘toggled’ by this method when commissioning for example.
Note that the motor must be stopped before changeover is allowed.
RESET
DATA
ENT