Chapter 4 Software index
4-18
Preset Speed
Command 3
Set value = 004
Preset Speed
Command 2
Set value = 003
Preset Speed
Command 1
Set value = 002
Jog Frequency
Command
Set value = 005
Output frequency
set value
X X X 1 b44
0 0 0 0
b45
0 0 1 0
b46
0 1 0 0
b47
0 1 1 0
b48
1 0 0 0
b49
1 0 1 0
b50
1 1 0 0
b51
1 1 1 0
b52
b35 ~ b38 (or b41) = 006: Emergency Stop (E.S)
The
iDrive
will decelerate the motor to stop on receiving the external emergency stop signal.
The display will be flashing ‘E.S.’
The
iDrive
will only start the motor again when the Emergency Stop signal is removed and the start
signal is turned off and then on again (remote start mode) or the Run key is pressed in (keypad mode).
Removing the Emergency Stop signal before the
iDrive
has fully stopped the motor will not inhibit the
Emergency Stop operation.
Output relay can be set to Emergency Stop fault by setting b55 = 008
b35 ~ b38 (or b41) = 007
:
Base Block (b.b.)
The
iDrive
will stop the motor immediately on receiving a Base Block signal regardless of
setting of b92 and display flashes ‘
b.b.
’ The
iDrive
auto restarts in speed search when b.b. is
signal removed.
b35 ~ b38 (or b41) = 008: Switching to Acceleration time 2 / Deceleration time 2
When terminal is ON the 2nd acceleration / deceleration ramps are selected.
b35 ~ b38 (or b41) = 009: Reset command
Reset command ON. The
iDrive
output will be disabled. Resettable faults will be cleared.
b35 ~ b38 (or b41) = 010 / 011: UP / DOWN function:
(According to acceleration/deceleration time)
Set A01 = 003,
to enable UP/DOWN function. The UP/DOWN key on Keypad is unavailable for
changing frequency directly in this mode.
Set b42 = 000,
When an UP/DOWN signal is ON, the
iDrive
accelerates / decelerates the motor to a
frequency and stops accelerating / decelerating when the UP/ DOWN signal is removed. The motor
will continue at this speed until another command is given.
The
iDrive
will decelerate the motor to stop or free run to stop when the run command is OFF
according to b92. The frequency at which the
iDrive
stops the motor will be stored in b45.
In this mode the UP/DOWN key is unavailable for modifying frequency. Use b45 to modify.
Set b42 = 001,
The
iDrive
will run from 0Hz on receiving a run command
.
UP/DOWN action is similar to above description. When the run command is removed, the motor will
decelerate to stop or free run to stop (0 Hz) according to setting of b92.
The
iDrive
will output from 0Hz in next operation.
Note: UP/ DOWN commands are disabled if both terminals are ON at the same time.
b35 ~ b38 (or b41) = 012: Control Signal Switch
Terminal OFF: Operation signal / frequency reference signal is controlled by A00/A01.
Terminal ON: Operation signal / frequency signal is controlled by keypad (not controlled by A00/A01).