You must connect the connector on the power cord that comes with your PDU to a
properly wired and grounded outlet. The following table shows illustrations of the
power cord connector and the correct outlet for each of the PDUs.
PDU
Plug
Outlet
Rating
v
DPI 32 amp/250 V 3-phase
Enterprise C13 PDU with IEC
309 3P+N+Gnd connector
v
DPI 32 amp/250 V 3-phase
Enterprise C19 PDU with IEC
309 3P+N+Gnd connector
L1
L2
L3
N
G
N
L1
L2
L3
G
32 amps,
220-240/380-415 V
ac
IEC 309
3P+N+Gnd
v
DPI 32 amp/250 V 1-phase
Enterprise C13 PDU with IEC
309 2P+N+Gnd connector
N
L
G
N
L
G
32 amps, 250 V ac
IEC 309 P+N+Gnd
v
DPI 63 amp/250 V 1-phase
Enterprise C13 PDU with IEC
309 2P+N+Gnd connector
v
DPI 63 amp/250 V 1-phase
Enterprise C19 PDU with IEC
309 2P+N+Gnd connector
N
L
G
N
L
G
63 amps, 250 V ac
IEC 309
3P+N+Gnd
v
DPI 30 amp/208 V 1-phase
Enterprise C13 PDU with
Nema L6-30P connector
G
X
Y
G
X
Y
30 amps, 250 V ac
NEMA L6-30
v
DPI 60 amp/208 V 1-phase
Enterprise C13 PDU with IEC
309 2P+Gnd connector
v
DPI 60 amp/208 V 1-phase
Enterprise C19 PDU with IEC
309 2P+Gnd connector
L2
L1
G
L2
L1
G
60 amps, 250 V ac
IEC 309 2P+Gnd
v
DPI 60 amp/208 V 3-phase
Enterprise C19 PDU with IEC
309 3P+Gnd connector
v
DPI 60 amp/208 V 3-phase
Enterprise C13 PDU with IEC
3P+Gnd connector
L3
L2
L1
G
L2
L3
G
60 amps, 208 V ac
IEC 309 3P+Gnd
Chapter 8. PDU specifications