Chapter 3. Installing the PDU horizontally in a rack cabinet
Attention:
Horizontal installation of a PDU is not supported during relocation or
shipping of a rack cabinet. You must remove any horizontally mounted PDUs from
the EIA mounting space before you relocate the rack cabinet.
Note:
Removing the rack doors and side panels might make installation easier.
See the rack cabinet documentation for more information.
Review the documentation that comes with your rack cabinet for safety and cabling
information. When you install the PDU in a rack cabinet, observe the following
precautions:
v
Make sure that the room air temperature is below 35°C (95°F).
v
Do not block any air vents; usually 15 cm (6 in.) of air space provides proper
airflow.
v
Plan the device installation starting from the bottom of the rack cabinet.
v
Install the heaviest device in the bottom of the rack cabinet.
v
Do not extend more than one device out of the rack cabinet at the same time.
v
Connect all power cords to properly wired and grounded electrical outlets.
v
Do not overload the power outlet when you install multiple devices in the rack
cabinet.
Use cage nuts for rack cabinets with square holes, and use clip nuts for rack
cabinets with round holes. If your rack cabinet requires cage nuts, use a
cage-nut-insertion tool or a flat-blade screwdriver to install them.
Cage
nuts
Cage
nuts
Clip
nuts