Installing the PDU in the side of a rack cabinet
The mounting holes on the upper and lower side braces in a rack side compartment
must be between 48.6 cm (19.1 in.) and 56.9 cm (22.4 in.) apart. If your rack
cabinet has movable side braces, see the rack cabinet documentation for
information about relocating the side braces if they are not already spaced for this
installation.
Note:
Removing the rack doors and side panels might make installation easier.
See the rack cabinet documentation for more information.
Review the documentation that comes with your rack cabinet for safety and cabling
information. When you install the PDU in a rack cabinet, observe the following
precautions:
v
Make sure that the room air temperature is below 35°C (95°F).
v
Do not block any air vents; usually 15 cm (6 in.) of air space provides proper
airflow.
v
Connect all power cords to properly wired and grounded electrical outlets.
v
Do not overload the power outlet when you install multiple devices in the rack
cabinet.
To install a PDU in the side of a rack cabinet by using the vertical mounting
brackets, complete the following steps:
1. Align the vertical mounting brackets to the front of the PDU and attach the
brackets to the PDU with two M3 x 5 screws per bracket. Use the screws that
come with the PDU. You can install the PDU in a rack cabinet with the power
outlets facing the rear or the front of the rack cabinet.
LA
N
3
4
1
2
5
6
12
DPI C13 PDU+, DPI C13 3-phase PDU+, DPI C19 PDU+, and DPI C19 3-phase PDU+: Installation and Maintenance Guide