4. General description
Installation instructions TERRA AL 60 Max
20
The minimum distances must be respected, because of the case of maintainance and to
prevent air-short-circuits.
view from above
suction
suction
exhaust
exhaust
wind direction
wind direction
min.
2000 mm
3270 mm
920 mm
min. 200 mm
min. 800 mm
min. 1000 mm
condensation outlet
heating side and electri-
cal connections
Placement and Installation
4.10. Wind direction
When installing in windy areas (eg on the roof), the orientation of the machine must be selected in such a way
that the expected wind direction is turned by 90 degrees to the suction/exhaust direction of the heatpump.
4.11. Decoupling from the building
The heat pump must be decoupled from the building in order to avoid structure borne noise. For example
when installing on a
fl
at roof
4.12. Space requirements
In order to guarantee maintenguarantee maintenance and operation of the heat pump, following minimum
distance has to be observed (for operation and maintenance). By observing this distance an unobstructed
system maintenance and operation can be guaranteed.