Placement and Installation
4.9. Foundation construction
The ground must be a
fi
rm and level surface. It is possible to install concrete bases or other good bearing
components. The load capacity must be guaranteed.
The air source heat pump have to be positioned at least 20 cm higher the the surrounnding area.
If the base is lower than the expected snow level, the suction must be kept free of snow snowfall.
The maximum length of the hydraulic interconnections between Hygienik or heating bu
ff
er and
heat pump must not exceed 35 m. Please note when planing the position of the concrete base.
The charging pump must be dimensioned accordingly.
The condensation run o
ff
and the hydraulic and electric connections are located on the rear
(air inlet) of the heat pump.
Bottom view
2 x condensate run o
ff
hydraulic and electrical
connections
air inlet
(evaporator)
air outlet
(fan)
height adjustable
base feet (4 pcs.)