3 CC-Link IE Field Basic Communication (Slave)
KW2D Series Smart RFID Reader User’s Manual
4-19
4
Co
m
m
un
ica
tio
n F
un
ctio
n
3.1 Overview
The KW2D Series Smart RFID Reader supports CC-Link IE Field Basic communication (slave station).
KW2D Series Smart RFID reader works as a slave station in CC-Link Field Basic communication and communication can
be performed with CC-Link Field Basic devices such as programmable displays or PLCs.
●
Communication Specifications
●
CC-Link IE Field Basic Communication Shared Memory
CC-Link IE Field Basic shared memory for communication is a memory that can be accessed by CC-Link IE Field Basic
master.
When
CC-Link IE Field Basic Slave
is selected in
Communication Mode
of
Connection Settings
on
RFID
Reader Settings
tab, the shared memory of the KW2D Smart RFID Reader is read or written via CC-Link IE Field
Basic Slave shared memory. The assignment of the shared memory is as follows.
3
CC-Link IE Field Basic Communication (Slave)
*1 Can be changed with the KW RFID Configurator
Items
Specifications
Supported protocols
CC-Link IE Field Basic (Slave Station)
Supported ports
Ethernet port
Action
Slave Station
Port number
61450 (for cyclic transmission), 61451 (for device detection)
Number of connections
1 (number of occupied stations: 1)
Send wait time
0 to 255ms (default 0ms)
RX
64 bits
RWr
32 words
Cyclic data (1 station)
RY
64 bits
RWw
32 words
Shared Memory
CC-Link IE Field Basic Slave
Device Name
Address No.
Device Name
Address No.
Input Relay
0001 to 0016
RX
0 to 0F
0017 to 0032
10 to 1F
0033 to 0064
20 to 3F
Input Register
0001 to 0032
RWr
0 to 1F
Coil Relay
0001 to 0016
RY
0 to 0F
0017 to 0064
10 to 3F
Holding Register
0001 to 0032
RWw
0 to 1F
When the power is turned on or reset, the initial value is set in the shared memory.