52
Innovative Circuit Technology Ltd.
Output Grounding:
Power Modules are floating, may be
connected with Positive or Negative
ground
Alarm Output:
Form-C contact, 0.5A 60Vdc max
DC Connectors: (Output, Battery)
Bus Bar, 5/16” bolt hole
Load Dist. Module (LDM) Connectors:
8 terminal cage clamp style, 22-
12AWG, 0.51Nm max torque
Alarm Output Connector:
3 pin removable plug, cage clamp
type 16
–
24 AWG
Alarm input, Bat temp sense Connector:
7 pin removable plug, cage clamp
type 16
–
24 AWG
Operating Temperature Range:
-30C to +60°C
6
Storage Temperature Range:
-40 to +70°C
Humidity:
(Operating)
10
–
90% (non-condensing)
(Storage)
5
–
95% (non-condensing)
Cooling:
Load controlled fan on power
modules
Regulatory Compliance:
UL/CSA 60950-1, UL/CSA 62368-1,
ICES-003, FCC Part 15/B, EN 61000-
6-2 and EN 61000-6-3
Network Communication:
RJ45 10/100-T port (IPv4, HTTP,
HTTPS, SMTP, DNS, TCP, UDP, ICMP,
DHCP, ARP, SNMP, SNTP Protocols)
5
AC mains power off; backup battery connected; LVD open
6
De-rate output 2% per °C above 50°C
Power System
12V
Module
24V
Module
48V Module
BMMD Max total Battery
Current through LVD
150A
-
-
BMMD LVD Threshold V
(Default)
-
11.5V
23.0V
46.0V
BMM LVD Reconnect V
(Default setting)
-
12.5V
25V
50V
BMMD idle DC Power Draw
5
<1W
-
-
LDM Max Load per Output
(continuous)
-
25A
25A
25A