50
Innovative Circuit Technology Ltd.
Battery Management Module (BMMD) Alarms:
Alarm Condition
Trigger Condition
LVD
Contactor
ICM
Required
Alarm
Relay
Send
3
Module Power
Failure
Loss of AC, and battery
disconnected
Open
No
-
Yes
No Alarms
Normal Operation
Closed
No
No
-
Battery Low SOC
SOC drops below Low
SOC setting
Closed
Yes
Active
3
Yes
Battery
Overcurrent
Battery I rises above OC
setting for 10s
Closed
Yes
Active
4
Yes
Circuit Breaker
Open
Circuit breaker trips or
manually opened
Open
Yes
Active
4
Yes
Battery Over
Temperature
Optional TMP probe
temp >50C for 5s
Open
Yes
Active
4
Yes
LVD
Battery V at LVD or
Overvoltage setting
Open
No
Active
Yes
Configuration
Error
Mixed polarity modules,
or installed in slot 1, 2,
5, or 6
Open
No
Active
Yes
Load Distribution Module (LDM) Alarms:
Alarm Condition
Trigger Condition
Output
Relays
ICM
Required
Alarm
Relay
Send
3
Module Power
Failure
Loss of AC and DC bus
connection
Open
No
-
Yes
No Alarms
Normal Operation,
outputs enabled
Closed
No
No
-
Circuit Breaker
Open
Circuit breaker opened
or tripped
Closed
Yes
Active
4
Yes
Output
Undercurrent
Output current drops
below setting for 5s
Closed
Yes
Active
4
Yes
Output
Overcurrent
Output current rises
above setting for 5s
Closed
Yes
Active
4
Yes
Configuration
Error
Mixed polarity modules,
or installed in slot 1, 2,
5, or 6
No
change
Yes
Active
4
Yes
Load Shedding
V drops below Load
Shed setting for 30s
Open
Yes
Active
4
Yes
Output Manually
Disabled
Output manually
disabled via ICM or GUI
page
Open
Yes
-
-
Intelligent Control Module (ICM) Alarms:
Alarm Condition
Trigger Condition
Alarm Relay
Send Email
3
Alarm Input
Contact open or close on any
Alarm input 1 to 4
Active (if set up on
Alarm Input page)
Yes
AC Input Failure
AC input falls below 90Vac
Active
Yes
3
Contact active only if alarm enabled in the Network GUI module Setup page