34
Innovative Circuit Technology Ltd.
Multiple outputs channels with power cycling enabled that are disabled will
be re-enabled in sequence from output #1 to #4. This feature is useful for
remotely resetting power to a router or other hardware required for the
network connectivity of the panel.
Output #_ Load-Shedding
Enable Load-Shedding
: Check this box to disable an output channel when the
bus voltage drops below the load-shedding threshold for at least 30s. This
feature can be used to disconnect less critical loads to preserve back-up
battery power as the battery voltage drops when the AC power has failed.
Load-Shedding Threshold
: Enter the voltage level at which a selected output
channel will be disconnected.
Recovery Threshold
: Enter the voltage level at which a selected output
channel will automatically be reconnected. This value must be at least 0.5V
above the
Load-Shedding Threshold
voltage.
Enable Load-Shedding upon AC Failure condition:
Check this box to disable
the output when an AC failure condition is detected and persists for at least
30s. If this option is checked, the Load-Shedding DC bus voltage thresholds
are not used and will be greyed out.
Load-Shedding Auto Recovery
: Check this box to allow an output channel to
be automatically reconnected when the bus voltage is above the
Recovery
Threshold
for at least 60s. If the
“
Enable Load-Shedding upon AC Failure
condition”
option is selected, the output will instead be reconnected when
AC input power is restored. The output channel must be manually re-enabled
using the
Module Output Control On
button in the
Module Control
section
if the
Auto Recovery
function is not enabled.
Output #_ Over-Current Alarm
Over-Current Threshold
: Enter the over-current level.at which the alarm will
trigger. Output current must remain at or above this level for at least 5s to
trigger the Over-Current Alarm. Disable this alarm by setting the threshold to
0A (default).
Disable this Output:
Check this box to automatically disable the output for
an over-current condition on the selected output channel. This function may
be used as an electronic circuit breaker which can then be remotely reset by
clicking the
Module Output Control On
button in the
Module Control
section.
Output #_ Under-Current Alarm
Under-Current Threshold
: Enter the under-current level.at which the alarm
will trigger. Output current must remain at or below this level for at least 5s