Innovative Circuit Technology Ltd.
35
to trigger the Under-Current Alarm. Disable this alarm by setting the
threshold to 0A (default).
Click the
Save Settings
button to save the configuration for that output channel,
and then repeat the setup process for each of the 4 output channels to be used.
Alarms
The
STATUS
tab displays the current state and history of the alarms.
Click on the
SETTINGS & CONTROL
tab to configure the input alarm settings. Click
on the
Save Settings
button at the bottom of the page to store your changes.
Alarm Input #_
Alarm Name:
Enter a descriptive name for the selected alarm input that suits
the installation if desired (this will be used for e-mailed alarm messages).
Contact Type:
Select either
Normally Open (N.O.)
or
Normally Closed (N.C.)
for the device to be monitored, or
Not Used
if the alarm input is unused
(default setting).
Activate Alarm Form C Contact:
Check this box (default) to have the back
panel alarm contacts change state for an alarm condition.