ECAT-2011H EtherCAT Slave I/O module
Copyright © 2018 ICP DAS CO., Ltd. All Rights Reserved.
-
23 -
AD Range Selection
The ECAT-2011H provides Analog Input voltage range of
±10 V, ±5 V, ±2.5 V, 0 ~ +10 V and
Analog
Input currnet range of
±20 mA, 0 ~ +20 mA, +4 ~ +20 mA.
Th
e factory default a setting is
±
10 V
.
Refer to the following instructions for details of how to change the AD range.
In the left-hand window, click the
“Box 1 (ECAT-2011H 16S.E./8Diff Ch. Ana.)”
itme. (See Figure
3-3.3)
In the right-hand window, click the
“CoE – Online”
tab. (See Figure 3-3.4)
Double-click
the
“Index
8000:19 (AI Range)”
to open the
“Set Value Dialog”
box.
Select the
AI range value (e.g.,
±5 V
)
from the
“Enum”
drop down options and then click the
“OK”
button.
Figure 3-3.8