A-11. CL-212 / CL-212-E DCON Command Sets
- 143 -
Command
Description
@AACLCN
Clear low latched alarm of a channel,
N = 2 for relative humidity,
3 for temperature in 0.01°C,
4 for temperature in 0.01°F,
5 for dew point temperature in 0.01°C,
6 for dew point temperature in 0.01°F
@AADACN
Disable AI alarm of a channel,
N = 0 for CO
2
In 1ppm,
1 for PM2.5 in 1 ug/m3,
2 for relative humidity in 0.01%,
3 for temperature in 0.01°C,
4 for temperature in 0.01°F,
5 for dew point temperature in 0.01°C,
6 for dew point temperature in 0.01°F
@AADI
read DO
response
!AA00O00
@AADLB
Read the beginning of the period setting of the data logger for
period logging mode
response
!AAyyyymmddhhmmss,
@AADLByyyymmd
dhhmmss
Set the beginning of the period setting of the data logger for period
logging mode
yyyy: year, 2000 to 2199, mm: month, 01 to 12, dd: date, 01 to 31,
hh: hour, 0 to 24, mm: minute, 0 to 59, ss: second, 0 to 59
@AADLC
Read the data logger command
response
!AAh, 0: stop, 1: run, 2: run in period mode
@AADLCh
Set the data logger command, h->0: stop, 1: run, 2: run in period
mode
@AADLE
Read the ending of the period setting of the data logger for period
logging mode
response
!AAyyyymmddhhmmss