C-3. CL-203-E Modbus Address Mappings (Base 1)
- 169 -
Address Description
Attribute
40486
RS-485 baud rate and parity settings
Bits 5:0
Baud rate, valid range: 3 ~ 10
Bits 7:6
00: no parity, 1 stop bit
01: no parity, 2 stop bit
10: even parity, 1 stop bit
11: odd parity , 1 stop bit
Only for Modbus RTU protocol
R/W
40488
RS-485 response delay time in ms, valid range, 0 ~ 30
Only for Modbus RTU protocol
R/W
40489
RS-485 host watchdog timeout value, 0 ~ 255, in 0.1s
Only for Modbus RTU protocol
R/W
40492
RS-485 host watchdog timeout count, write 0 to clear
Only for Modbus RTU protocol
R/W
40496
Automatic baseline correction for CO2 measurement, 0: disable,
1:enable
R/W
40497
Beep on alarm, 0: disable, 1 to 250: beep on alarm time in
seconds, 251: beep on alarm continuously
R/W
30513 ~
30519
40513 ~
40519
High latched analog input value of channel 0 to 6
R
30545 ~
30551
40545 ~
40551
Low latched analog input value of channel 0 to 6
R
30556
40556
Module reset status, 1: power-on, 2: watchdog, 3: software reset
command
Only for Modbus TCP protocol
R
40558
Ethernet host watchdog timeout value, 5 to 65535, in second, 0 to
disable.
Only for Modbus TCP protocol
R/W
30559
40559
Ethernet host watchdog timeout count.
Only for Modbus TCP protocol
R
30560
40560
Module name, 0x0203
Only for Modbus TCP protocol
R