![ICP DAS USA CL-200 Series User Manual Download Page 99](http://html1.mh-extra.com/html/icp-das-usa/cl-200-series/cl-200-series_user-manual_614324099.webp)
A-3. CL-203-E DCON Command Sets
- 99 -
Command
Description
@AADI
read DO
response
!AA00O00
@AADLB
Read the beginning of the period setting of the data logger for
period logging mode
response
!AAyyyymmddhhmmss,
@AADLByyyymmd
dhhmmss
Set the beginning of the period setting of the data logger for period
logging mode
yyyy: year, 2000 to 2199, mm: month, 01 to 12, dd: date, 01 to 31,
hh: hour, 0 to 24, mm: minute, 0 to 59, ss: second, 0 to 59
@AADLC
Read the data logger command
response
!AAh, 0: stop, 1: run, 2: run in period mode
@AADLCh
Set the data logger command, h->0: stop, 1: run, 2: run in period
mode
@AADLE
Read the ending of the period setting of the data logger for period
logging mode
response
!AAyyyymmddhhmmss
@AADLEyyyymmd
dhhmmss
Set the ending of the period setting of the data logger for period
logging mode
yyyy: year, 2000 to 2199, mm: month, 01 to 12, dd: date, 01 to 31,
hh: hour, 0 to 24, mm: minute, 0 to 59, ss: second, 0 to 59
@AADLN
Read number of log records in the data logger
response
!AAhhhhhhhh, hhhhhhhh in hex format
@AADLO
Read the overwriting mode when data logger is full
response
!AAh, 0: stop logging when full, 1: overwrite
@AADLOh
Set the overwriting mode when data logger is full
h->0: stop logging when full, 1: overwrite
@AADLP
Read the samplig period setting of the data logger
response
!AAhhmmss, hh: hour, 0 to 24, mm: minute, 0 to 59, ss: second,
0 to 59