background image

C-8. CL-208-E Modbus Address Mappings (Base 1)                               

                                  - 193 - 

Address  Description 

Attribute 

40564 

TCP disconnection timeout value, 5 to 65535, in second, 0 to 

disable. 

Only for Modbus TCP protocol 

R/W 

40565 

Module reset timeout value, 30 to 65535, in second, 0 to disable. 

Only for Modbus TCP protocol 

R/W 

40865 

RTC year, 2000 to 2159 

R/W 

40866 

RTC month, 1 to 12 

R/W 

40867 

RTC date, 1 to 31 

R/W 

40868 

RTC hour, 0 to 23 

R/W 

40869 

RTC minute, 0 to 59 

R/W 

40870 

RTC second, 0 to 59 

R/W 

40871 

Total number of log records, low word 

40872 

Total number of log records, high word 

40873 

The starting record to read log data, low word 

R/W 

40874 

The starting record to read log data, high word 

R/W 

40875 

The status of the data logging, 0: stopped, 1: running 

40876 

The data logger command, 0: stop, 1: run, 2: run in period mode 

R/W 

40877 

Continue writing when data logger is full, 0: no, 1: yes 

R/W 

40878 

Hour of the data logger sampling period, 0 ~ 24 

R/W 

40879 

Minute of the data logger sampling period, 0 ~ 59 

R/W 

40880 

Second of the data logger sampling period, 0 ~ 59 

R/W 

40881 

Starting year when logging in period mode, 2000 ~ 2159 

R/W 

40882 

Starting month when logging in period mode, 1 ~ 12 

R/W 

40883 

Starting date when logging in period mode, 1 ~ 31 

R/W 

40884 

Starting hour when logging in period mode, 0 ~ 23 

R/W 

40885 

Starting minute when logging in period mode, 0 ~ 59 

R/W 

40886 

Starting second when logging in period mode, 0 ~ 59 

R/W 

40887 

Ending year when logging in period mode, 2000 ~ 2159 

R/W 

40888 

Ending month when logging in period mode, 1 ~ 12 

R/W 

40889 

Ending date when logging in period mode, 1 ~ 31 

R/W 

40890 

Ending hour when logging in period mode, 0 ~ 23 

R/W 

40891 

Ending minute when logging in period mode, 0 ~ 59 

R/W 

40892 

Ending second when logging in period mode, 0 ~ 59 

R/W 

40929 

The first fan off period in a day, beginning hour, 0 ~ 23 

R/W 

40930 

The first fan off period in a day, beginning minute, 0 ~ 59 

R/W 

40931 

The first fan off period in a day, ending hour, 0 ~ 23 

R/W 

Summary of Contents for CL-200 Series

Page 1: ...CL 200 Series User Manual Remote CO CO2 NH3 H2S HCHO TVOC Temperature Humidity Dew Point Data Logger Module Version 1 2 0 Date Feb 2019...

Page 2: ...reserves the right to change this manual at any time without notice The information furnished by ICP DAS is believed to be accurate and reliable However no responsibility is assumed by ICP DAS for it...

Page 3: ...n via Wi Fi 66 6 Monitoring via Mobile Devices 72 7 Utility to Get Manage Data Log 73 8 FAQ 84 Q1 What is ABC Automatic Baseline Correction 84 Q2 Why I need to enable the ABC 84 Q3 Does the CL 202 CL...

Page 4: ...2 CL 202 E Modbus Address Mappings Base 1 164 C 3 CL 203 E Modbus Address Mappings Base 1 168 C 4 CL 204 E Modbus Address Mappings Base 1 172 C 5 CL 205 E Modbus Address Mappings Base 1 176 C 6 CL 206...

Page 5: ...essed from the CL 200 data logger from anywhere and at any time using the free Windows software the iOS App or the Android App as long as they are connected to the same local network as the data logge...

Page 6: ...O Metal Oxide Sensor Able to store up to 450 000 records Remote control with a standard web browser iAir App for iOS or Android mobile devices to monitor on line data Supports the DCON Modbus RTU Modb...

Page 7: ...inal Please note that the web server is only available to the Ethernet interface Get Real time Data Anywhere and Anytime iAir App for iOS or Android Phones or Tablets is free and easy to install it ca...

Page 8: ...CL 202 CL 212 CL 203 CL 213 maintenance free In most indoor applications the carbon dioxide level drops to nearly outside air 400 ppm and then the ABC algorithm constantly keeps track of the lowest re...

Page 9: ...It can be used to provide up to 11 Mbps for IEEE 802 11b and 54 Mbps for IEEE 802 11g to connect to your wireless LAN MQTT is a protocol designed for the efficient exchange of real time data with sen...

Page 10: ...t Range 0 to 100 RH Non condensing Resolution 0 1 RH Non condensing Accuracy 5 RH Non condensing Dew Point Range Calculated using temperature and relative humidity Resolution 0 1 C System CO Alarm Yes...

Page 11: ...Wall Mounting Environment Operating Temperature 0 to 50 C Storage Temperature 30 to 75 C Humidity 10 to 90 RH Non condensing Model CL 202 E CL 202 BLE CL 202 WF CO2 Measurement Range 0 9999 ppm Resol...

Page 12: ...tooth Wi Fi Standard Supported BT 4 0 IEEE 802 11 b g n Wireless Mode Slave Infrastructure Limited AP Wireless Security AES 128 WEP WPA WPA2 Transmission Range 20 m LOS 50 m LOS Electrical Powered via...

Page 13: ...surement Range 10 to 50 C Resolution 0 1 C Accuracy 0 6 C Relative Humidity Measurement Range 0 to 100 RH Non condensing Resolution 0 1 RH Non condensing Accuracy 5 RH Non condensing Dew Point Range C...

Page 14: ...Mechanical Dimensions D x H 150 mm x 53 mm Installation Ceiling Mounting or Wall Mounting Environment Operating Temperature 0 to 50 C Storage Temperature 30 to 75 C Humidity 10 to 90 RH Non condensin...

Page 15: ...ol DCON Modbus RTU Modbus TCP MQTT Wire Interface Yes RS 485 X 1 and Ethernet PoE X1 Wireless Interface Bluetooth Wi Fi Standard Supported BT 4 0 IEEE 802 11 b g n Wireless Mode Slave Infrastructure L...

Page 16: ...5 RH Non condensing Dew Point Range Calculated using temperature and relative humidity Resolution 0 1 C System NH3 Alarm Yes PM2 5 Alarm Real Time Clock Yes Data Logger Yes 450 000 Records Alarm Relay...

Page 17: ...BLE CL 206 WF H2S Measurement Range 0 to 100 ppm Electrochemical Resolution 1 ppm Accuracy 5 of measured value Response Time 120 Sec Warm up Time 180 Sec Temperature Measurement Range 10 to 50 C Resol...

Page 18: ...Powered via PoE IEEE 802 3af Class 1 require a PoE switch or injector Power Consumption 1 9 W 2 2 W 2 2 W Mechanical Dimensions D x H 150 mm x 53 mm Installation Ceiling Mounting or Wall Mounting Env...

Page 19: ...Interface Yes RS 485 X 1 and Ethernet PoE X1 Wireless Interface Bluetooth Wi Fi Standard Supported BT 4 0 IEEE 802 11 b g n Wireless Mode Slave Infrastructure Limited AP Wireless Security AES 128 WEP...

Page 20: ...sing Accuracy 5 RH Non condensing Dew Point Range Calculated using temperature and relative humidity Resolution 0 1 C System HCHO Alarm Yes TVOC Alarm Yes PM2 5 Alarm Real Time Clock Yes Data Logger Y...

Page 21: ...ty 10 to 90 RH Non condensing Model CL 210 E CL 210 BLE CL 210 WF PM2 5 Measurement Range 0 to 400 ug m3 Resolution 1ug m3 Response Time 1 min Temperature Measurement Range 10 to 50 C Resolution 0 1 C...

Page 22: ...lock 12 to 48 VDC Powered via PoE IEEE 802 3af Class 1 require a PoE switch or injector Power Consumption 1 7 W 1 8 W 1 8 W Mechanical Dimensions D x H 150 mm x 53 mm Installation Ceiling Mounting or...

Page 23: ...0 Records Alarm Relay Output Form A 1 SPST 30 VDC 16 A or 250 VAC 16 A Communication Protocol DCON Modbus RTU DCON Modbus RTU Modbus TCP MQTT Wire Interface Yes RS 485 Yes RS 485 X 1 and Ethernet PoE...

Page 24: ...ponse Time 1 min CO2 Measurement Range 0 9999 ppm Resolution 1 ppm Accuracy 40 ppm 3 Response Time 120 seconds Warm up Time 5 minutes Temperature Measurement Range 10 to 50 C Resolution 0 1 C Accuracy...

Page 25: ...ion Range 20 m LOS 50 m LOS Electrical Powered via Terminal Block 10 to 30 VDC 12 to 48 VDC Powered via PoE IEEE 802 3af Class 1 require a PoE switch or injector Power Consumption 1 2 W 2 1 W 2 2 W 2...

Page 26: ...nsing Accuracy 5 RH Non condensing Dew Point Range Calculated using temperature and relative humidity Resolution 0 1 C System CO Alarm Yes CO2 Alarm Yes PM2 5 Alarm Yes Real Time Clock Yes Data Logger...

Page 27: ...30 VDC 12 to 48 VDC Powered via PoE IEEE 802 3af Class 1 require a PoE switch or injector Power Consumption 1 2 W 2 1 W 2 2 W 2 2 W Mechanical Dimensions D x H 150 mm x 53 mm Installation Ceiling Moun...

Page 28: ...DIP Switch The functions are printed on the right beside the SW1 DIP switch PoE non PoE Ethernet port The Ethernet port can be used to connect to a PoE switch or a non PoE switch DIP Switch Rotary Sw...

Page 29: ...tput Relay Output Wire Connection The Push in connector can easily connect and detach solid wires or wires with wire end ferrules without using tools Just push in the solid wire to lock it and press t...

Page 30: ...CL 200 Series User Manual Version 1 2 0 Apr 2019 30 2 3 Dimensions unit mm...

Page 31: ...ions near a strong electromagnetic field For connecting with a PC or a Android device The CL 200 logger can connect to a PoE network without a power source or connect to a non PoE network When using t...

Page 32: ...0 in the subnet mask For example in an entire IPv4 subnet the host PC or the Android device uses the private IP address space 172 16 0 0 12 and subnet mask address 255 240 0 0 the broadcast address is...

Page 33: ...th power input requirement of 12 48 VDC The CL 200 WF device can be configured as station mode such that the PC Laptop can be connected through Wi Fi AP The CL 200 WF device can be configured as AP mo...

Page 34: ...CL 200 Series User Manual Version 1 2 0 Apr 2019 34 2 5 Hardware Mounting...

Page 35: ...CL 200 Series User Manual Version 1 2 0 Apr 2019 35 Requires RJ45 Cable Male Female 30cm 90...

Page 36: ...tion is only available to the Ethernet interface 3 1 Search the CL 200 logger eSearch is designed to search out the CL 200 logger connected on the same Ethernet network it supports for Linux and Windo...

Page 37: ...as and click the OK button The Alias for easy to identify each item will be shown at the bottom left corner of the CL 200 screen 3 2 Logging into the CL 200 1 Enter the IP address for your CL 200 in t...

Page 38: ...ue Low Latched and maximum value High Latched logged Clicking on the Clear Low Latched button and the Clear High Latched button can reset the latched data to current value and latch new minimum or max...

Page 39: ...t disabled If one of the alarm modes is enabled the relay is linked to the alarm status for tapping audible visual alarm At the end of the page are the data time and device online time since powered o...

Page 40: ...e TCP Timeout Sets the timeout for disconnecting a TCP connection when a CL 200 does not receive data coming from the Ethernet port Range 5 65535 unit second 0 Disable 180 Web Auto logout Sets the tim...

Page 41: ...settings to factory default values Item Factory Default IP address type Static IP Static IP 192 168 255 1 Default gateway 192 168 0 1 Subnet Mask 255 255 0 0 MAC address Factory MAC address Modbus TCP...

Page 42: ...comes an OASIS standard it is an ideal protocol for communicating with connected devices in the emerging machine to machine M2M and Internet of Things applications and for mobile applications where ba...

Page 43: ...pic Name sets the sub topic name for each item A MQTT client subscribes the messages form a MQTT broker by specifying the topic name as Module Topic Name Sub Topic Name For example to subscribe the CO...

Page 44: ...y outside air where there are no human green plants or anything to elevate the carbon dioxide levels on weekday evenings or weekends the ABC algorithm constantly keeps track of the lowest reading and...

Page 45: ...ound alarm beeps as the setting in Beep on Alarm Time for CO CO2 high limit alarm events during the alarm stage Latched If a measurement value higher than the High Alarm Limit or lower than the Low Al...

Page 46: ...e the beeping alarm without stop 30 Set the Power On Value and Safe Value for the relay output and the Host Watchdog Timeout timer for RS 485 communication if a host does not send a command over the s...

Page 47: ...ettings take effect after clicking the Update Settings button Item Description Default Status Running the data logger is running Stopped the data logger is stopped Change Logging Sets the mode for dat...

Page 48: ...ones No Sampling Interval Sets the time interval for logging data It is valid for both Run mode and Period mode Sampling Interval Hour sets the hour for log interval Sampling Interval Minute set the...

Page 49: ...er Filter Settings 1 Select the radio button for Add ___ ___ ___ ___ To The List and type the IP address for the accessible device in the following text box 2 Click on the Submit button to the setting...

Page 50: ...me whoever wants to change to settings from the touch screed the password will be requested Change Web Password The password for logging into the web page is Admin and can be changed in the Change Web...

Page 51: ...CL 200 Series User Manual Version 1 2 0 Apr 2019 51 3 9 Logout Click the Logout on any page to logout the CL 200...

Page 52: ...f the parameters contained in the Wi Fi Status section Item Description Connection Status The Wi Fi connection status of the CL 200 WF device Signal Strength The Wi Fi signal strength of the CL 200 WF...

Page 53: ...used to secure wireless computer network It can be open WEP or WPA WPA2 It is recommended to use WPA WPA2 if possible DHCP Server AP Mode This parameter is used to specify whether to turn on the DHCP...

Page 54: ...tional networks SSID This parameter is used to specify the Service Set Identifier For station mode specify the SSID of the AP you would like to connect For AP mode the SSID will be used by the device...

Page 55: ...multiple CL 200 loggers connected to the same RS 485 network each logger needs be set with a unique RS 485 address More than one module having the same address will cause communication failure Testin...

Page 56: ...r Manual Version 1 2 0 Apr 2019 56 4 Select the COM Port number used to connect the CL 200 logger 5 The Baud Rate is factory default to 9600 bps 6 Select the Protocol tab and check the protocol that s...

Page 57: ...200 Series User Manual Version 1 2 0 Apr 2019 57 7 Select the Format tab and check the parity that set in the logger 8 Click the Start Search icon 9 The CL 200 logger searched out will be listed as be...

Page 58: ...e Parity Checksum items marked with INIT means that when any of those items needs be modified the pin 4 INIT needs to be set in ON position and power cycle the logger then the item can be modified Aft...

Page 59: ...CL 200 Series User Manual Version 1 2 0 Apr 2019 59 Degree of offset Clear High Low Alarm Latch PM2 5 CO2 level Humidity Temperature and Dew point temperature...

Page 60: ...CL 200 Series User Manual Version 1 2 0 Apr 2019 60 Alarm tab Set Alarm Configurations Alarm Mode Low Limit High Limit Alarm Buzzer On...

Page 61: ...enabled the functions on this tab are all disabled as below If all the alarm events are disabled the functions are available as below When the buttons are clicked the DO status will be set as the Pow...

Page 62: ...o enable the Host watchdog 2 Check the checkbox next to Send Host OK to send the command 3 Uncheck the checkbox next to Send Host OK to stop sending command the Host watchdog timeout will occur and re...

Page 63: ...CL 200 Series User Manual Version 1 2 0 Apr 2019 63 Logger Configuration Set the logger configuration on this TAB...

Page 64: ...r 2019 64 System Tab Click the Edit button to enable settings on this tab Check Uncheck the item to Enable Disable ABC function For CL 202 E CL 212 E CL 203 E CL 213 E only Click the Apply button to s...

Page 65: ...is powered on with the pin 4 INIT in ON position the protocol is DCON address is 0 Baud Rate is 9600 bps Parity is set to N 8 1 and Checksum is disabled After configuring the communication parameters...

Page 66: ...Channel AP Mode 11 IP Address 192 168 255 1 Gateway Address 192 168 255 254 Subnet Mask 255 255 0 0 SSID CL 213 WF Modbus TCP Port 502 The Wi Fi IIOT Utility is provided to configure and test the CL...

Page 67: ...User Manual Version 1 2 0 Apr 2019 67 Select the Wi Fi network interface and click on the OK button Configure and Test the Module When the module is found click on the module name to enter the config...

Page 68: ...be used by the device to be connected Encryption This parameter is used to specify which security protocol is used to secure wireless computer network It can be open WEP or WPA It is recommended to us...

Page 69: ...ific IP address Subnet Mask This parameter is used to assign the subnet mask for the SL device The subnet mask indicates which portion of the IP address is used to identify the local network or subnet...

Page 70: ...70 In the Alarm form you can change the alarm related settings Click on the Set Alarm Configurations button to save the changes to the module In the DO form you can change the digital output status a...

Page 71: ...CL 200 Series User Manual Version 1 2 0 Apr 2019 71 In the Data Logger form you can change the data logger related settings Click on the Apply button to save the changes to the module...

Page 72: ...the real time data from CL 200 loggers by entering a specific IP address or by performing an automatic search for available devices If a CL 200 can t be searched in the iAir App please contact with t...

Page 73: ...200 logger and export the data to csv files for performing statistical analysis in Excel The DL 300 Utility can be obtained from http ftp icpdas com pub cd iiot utility 1 Run the DL 300_utility_setup_...

Page 74: ...d click the Add button to add the module in the utility 3 4 Highlight a module and click the Edit Device button to configure the module 3 5 Set the configuration and click on the OK button Note Consul...

Page 75: ...al Version 1 2 0 Apr 2019 75 4 Get real time data trend chart and alarm event 4 1 Click the List icon to obtain the real time data It also lists the connect status group information and IP address for...

Page 76: ...for CO CO2 level Temperature or Humidity to access the trend chart for those real time data check the checkbox next to each CL 200 logger to display its trend chart or uncheck it to cancel display Dr...

Page 77: ...et the CO CO2 Alert Value CO CO2 Alarm Value If it is supported in the logger Temperature Alert Value and Temperature Alarm Value for trigger events Check the checkbox next to The Record Time Everyday...

Page 78: ...wnload data in a CL 200 logger and export the data 5 1 Select Update Database on the Settings menu 5 2 Click the Start button to download the data in CL 200 modules 5 3 Click the close icon to exit th...

Page 79: ...ser Manual Version 1 2 0 Apr 2019 79 5 4 Click the Query icon 5 5 Highlight the desired module set the Start Time and End Time and then click the Search button The data in the time period will be list...

Page 80: ...CL 200 Series User Manual Version 1 2 0 Apr 2019 80 5 6 Click the Export button to export the searched data in csv files for performing statistical analysis in Excel 6...

Page 81: ...2019 81 6 Group the devices by location or users 6 1 Select Group Settings on the Settings menu 6 2 Click the New button enter the group name and click the OK button in the pop up box and then click t...

Page 82: ...2019 82 6 3 Select Device Settings on the Settings menu highlight the desired device and click the Edit Device button select the group name for the module and click the OK button in the pop up Device...

Page 83: ...CL 200 Series User Manual Version 1 2 0 Apr 2019 83 6 4 Monitor the group data by clicking the Group icon and then highlighting the group name...

Page 84: ...to enable the ABC A2 When the CO2 concentration detected in a period time of unoccupied space is greater than the base value of 400ppm enable the ABC function to adjust the baseline Be careful that th...

Page 85: ...the submit button to save the IP setting and use after repowering Once any of those in the list is set only the device for which the IP address is saved in the list can assess the CL 200 Q6 How to del...

Page 86: ...2 0 Apr 2019 86 Q7 How to clear the data logged in a CL 200 module A7 Enter the IP address for the module in the address bar of a web browser and go to the I O Settings page click the Reset Data Logg...

Page 87: ...0 others AA Read All Analog Inputs response CO in 1 ppm relative humidity in 0 01 temperature in 0 01 C temperature in 0 01 F dew point temperature in 0 01 C dew point temperature in 0 01 F AAN Read C...

Page 88: ...elative humidity 2 for temperature in 0 01 C 3 for temperature in 0 01 F 4 for dew point temperature in 0 01 C 5 for dew point temperature in 0 01 F AACL Clear all low latched analog inputs to the cur...

Page 89: ...etting of the data logger for period logging mode yyyy year 2000 to 2199 mm month 01 to 12 dd date 01 to 31 hh hour 0 to 24 mm minute 0 to 59 ss second 0 to 59 AADLN Read number of log records in the...

Page 90: ...n 0 01 C 3 for temperature in 0 01 F 4 for dew point temperature in 0 01 C 5 for dew point temperature in 0 01 F AARACN Read AI alarm enabled disabled status of a channel response AAN N 0 disabled 1 m...

Page 91: ...og 1 enable host watchdog TT host watchdog timeout in 0 1s in hex format AA4 read DO power on and safe value AA50P0S set DO power on and safe value P 0 power on value off 1 power on value on S 0 safe...

Page 92: ...in 0 01 C temperature in 0 01 F dew point temperature in 0 01 C dew point temperature in 0 01 F AAN Read Channel Analog Input N 0 for CO2 in 1 ppm 1 for relative humidity in 0 01 2 for temperature in...

Page 93: ...relative humidity 2 for temperature in 0 01 C 3 for temperature in 0 01 F 4 for dew point temperature in 0 01 C 5 for dew point temperature in 0 01 F AACL Clear all low latched analog inputs to the cu...

Page 94: ...etting of the data logger for period logging mode yyyy year 2000 to 2199 mm month 01 to 12 dd date 01 to 31 hh hour 0 to 24 mm minute 0 to 59 ss second 0 to 59 AADLN Read number of log records in the...

Page 95: ...in 0 01 C 3 for temperature in 0 01 F 4 for dew point temperature in 0 01 C 5 for dew point temperature in 0 01 F AARACN Read AI alarm enabled disabled status of a channel response AAN N 0 disabled 1...

Page 96: ...og 1 enable host watchdog TT host watchdog timeout in 0 1s in hex format AA4 read DO power on and safe value AA50P0S set DO power on and safe value P 0 power on value off 1 power on value on S 0 safe...

Page 97: ...CO in 1 ppm CO2 in 1 ppm relative humidity in 0 01 temperature in 0 01 C temperature in 0 01 F dew point temperature in 0 01 C dew point temperature in 0 01 F AAN Read Channel Analog Input N 0 for CO...

Page 98: ...point temperature in 0 01 C 6 for dew point temperature in 0 01 F AACHCN Clear high latched alarm of a channel N 0 for CO 1 for CO2 2 for relative humidity 3 for temperature in 0 01 C 4 for temperatur...

Page 99: ...iod mode AADLE Read the ending of the period setting of the data logger for period logging mode response AAyyyymmddhhmmss AADLEyyyymmd dhhmmss Set the ending of the period setting of the data logger f...

Page 100: ...erature in 0 01 C 6 for dew point temperature in 0 01 F AAHO Read humidity offset AAHO data Set humidity offset data in format of 100 00 100 00 AALO data CN Set low alarm limit of an AI channel N 2 fo...

Page 101: ...t watchdog enable disable status and timeout value AA3ETT enable disable host watchdog and set timeout value E 0 disable host watchdog 1 enable host watchdog TT host watchdog timeout in 0 1s in hex fo...

Page 102: ...0 01 temperature in 0 01 C temperature in 0 01 F dew point temperature in 0 01 C dew point temperature in 0 01 F AAN Read Channel Analog Input N 0 for HCHO in 1 ppb 1 for TVOC in 1 ppb 2 for relative...

Page 103: ...ture in 0 01 F 5 for dew point temperature in 0 01 C 6 for dew point temperature in 0 01 F AACL Clear all low latched analog inputs to the current values AACLN Clear channel low latched analog input t...

Page 104: ...etting of the data logger for period logging mode yyyy year 2000 to 2199 mm month 01 to 12 dd date 01 to 31 hh hour 0 to 24 mm minute 0 to 59 ss second 0 to 59 AADLN Read number of log records in the...

Page 105: ...in format of 100 00 100 00 AALO data CN Set low alarm limit of an AI channel N 2 for relative humidity in 0 01 3 for temperature in 0 01 C 4 for temperature in 0 01 F 5 for dew point temperature in 0...

Page 106: ...sable status and timeout value AA3ETT enable disable host watchdog and set timeout value E 0 disable host watchdog 1 enable host watchdog TT host watchdog timeout in 0 1s in hex format AA4 read DO pow...

Page 107: ...in 0 01 temperature in 0 01 C temperature in 0 01 F dew point temperature in 0 01 C dew point temperature in 0 01 F AAN Read Channel Analog Input N 0 for NH3 in 1 ppm 1 for relative humidity in 0 01...

Page 108: ...ow latched analog inputs to the current values AACLN Clear channel low latched analog input to the current value N 0 for NH3 1 for relative humidity 2 for temperature in 0 01 C 3 for temperature in 0...

Page 109: ...hhh hhhhhhhh in hex format AADLO Read the overwriting mode when data logger is full response AAh 0 stop logging when full 1 overwrite AADLOh Set the overwriting mode when data logger is full h 0 stop...

Page 110: ...humidity in 0 01 2 for temperature in 0 01 C 3 for temperature in 0 01 F 4 for dew point temperature in 0 01 C 5 for dew point temperature in 0 01 F AAHO Read humidity offset AAHO data Set humidity of...

Page 111: ...dog status AA1 clear host watchdog timeout status AA2 read host watchdog enable disable status and timeout value AA3ETT enable disable host watchdog and set timeout value E 0 disable host watchdog 1 e...

Page 112: ...in 0 01 temperature in 0 01 C temperature in 0 01 F dew point temperature in 0 01 C dew point temperature in 0 01 F AAN Read Channel Analog Input N 0 for H2S in 1 ppm 1 for relative humidity in 0 01...

Page 113: ...ow latched analog inputs to the current values AACLN Clear channel low latched analog input to the current value N 0 for H2S 1 for relative humidity 2 for temperature in 0 01 C 3 for temperature in 0...

Page 114: ...hhh hhhhhhhh in hex format AADLO Read the overwriting mode when data logger is full response AAh 0 stop logging when full 1 overwrite AADLOh Set the overwriting mode when data logger is full h 0 stop...

Page 115: ...1 for relative humidity in 0 01 2 for temperature in 0 01 C 3 for temperature in 0 01 F 4 for dew point temperature in 0 01 C 5 for dew point temperature in 0 01 F AAHO Read humidity offset AAHO data...

Page 116: ...read host watchdog status AA1 clear host watchdog timeout status AA2 read host watchdog enable disable status and timeout value AA3ETT enable disable host watchdog and set timeout value E 0 disable ho...

Page 117: ...in 0 01 temperature in 0 01 C temperature in 0 01 F dew point temperature in 0 01 C dew point temperature in 0 01 F AAN Read Channel Analog Input N 0 for HCHO in 1 ppb 1 for relative humidity in 0 01...

Page 118: ...ture in 0 01 F 4 for dew point temperature in 0 01 C 5 for dew point temperature in 0 01 F AACL Clear all low latched analog inputs to the current values AACLN Clear channel low latched analog input t...

Page 119: ...etting of the data logger for period logging mode yyyy year 2000 to 2199 mm month 01 to 12 dd date 01 to 31 hh hour 0 to 24 mm minute 0 to 59 ss second 0 to 59 AADLN Read number of log records in the...

Page 120: ...0 to 59 The beginning hour minute should be earlier than the ending hour minute Otherwise the setting is ignored If all of the six period settings are invalid then the fan is controlled by the AAFNE c...

Page 121: ...format of 00100 00100 AATO Read temperature offset in 0 01 C AATO data Set temperature offset in 0 01 C 100 00 100 00 clear host watchdog timeout counter AA0 read host watchdog status AA1 clear host...

Page 122: ...in 0 01 temperature in 0 01 C temperature in 0 01 F dew point temperature in 0 01 C dew point temperature in 0 01 F AAN Read Channel Analog Input N 0 for TVOC in 1 ppb 1 for relative humidity in 0 01...

Page 123: ...ture in 0 01 F 4 for dew point temperature in 0 01 C 5 for dew point temperature in 0 01 F AACL Clear all low latched analog inputs to the current values AACLN Clear channel low latched analog input t...

Page 124: ...etting of the data logger for period logging mode yyyy year 2000 to 2199 mm month 01 to 12 dd date 01 to 31 hh hour 0 to 24 mm minute 0 to 59 ss second 0 to 59 AADLN Read number of log records in the...

Page 125: ...0 to 59 The beginning hour minute should be earlier than the ending hour minute Otherwise the setting is ignored If all of the six period settings are invalid then the fan is controlled by the AAFNE c...

Page 126: ...format of 00100 00100 AATO Read temperature offset in 0 01 C AATO data Set temperature offset in 0 01 C 100 00 100 00 clear host watchdog timeout counter AA0 read host watchdog status AA1 clear host...

Page 127: ...in 0 01 temperature in 0 01 C temperature in 0 01 F dew point temperature in 0 01 C dew point temperature in 0 01 F AAN Read Channel Analog Input N 0 for PM2 5 in 1 ug m3 1 for relative humidity in 0...

Page 128: ...ture in 0 01 F 4 for dew point temperature in 0 01 C 5 for dew point temperature in 0 01 F AACL Clear all low latched analog inputs to the current values AACLN Clear channel low latched analog input t...

Page 129: ...etting of the data logger for period logging mode yyyy year 2000 to 2199 mm month 01 to 12 dd date 01 to 31 hh hour 0 to 24 mm minute 0 to 59 ss second 0 to 59 AADLN Read number of log records in the...

Page 130: ...g hour minute should be earlier than the ending hour minute Otherwise the setting is ignored If all of the six period settings are invalid then the fan is controlled by the AAFNE command AAHI data CN...

Page 131: ...data AATO Read temperature offset in 0 01 C AATO data Set temperature offset in 0 01 C 100 00 100 00 clear host watchdog timeout counter AA0 read host watchdog status AA1 clear host watchdog timeout s...

Page 132: ...CON protocol N 0 DCON 1 Modbus RTU AA2 Reads configuration AA is the RS 485 address hex AA5 Reads reset status response AA1 first after power on AA0 others AA Read All Analog Inputs response CO in 1 p...

Page 133: ...rity 2 stop bits N 8 2 10 even parity 1 stop bit E 8 1 11 odd parity 1 stop bit O 8 1 FF data format Bit 6 0 checksum disabled 1 checksum enabled AABA Read beep on alarm time response AAHH HH in hex 0...

Page 134: ...of a channel N 0 for CO In 1ppm 1 for PM2 5 in 1 ug m3 2 for relative humidity in 0 01 3 for temperature in 0 01 C 4 for temperature in 0 01 F 5 for dew point temperature in 0 01 C 6 for dew point tem...

Page 135: ...data logger for period logging mode yyyy year 2000 to 2199 mm month 01 to 12 dd date 01 to 31 hh hour 0 to 24 mm minute 0 to 59 ss second 0 to 59 AADLC Read the data logger command response AAh 0 sto...

Page 136: ...ead logging status of the data logger response AAhh hh in hex format 00 stopped 01 running others error AADO0V set DO V 0 off 1 on AAEATCN Enable AI alarm of a channel N 0 for CO In 1ppm 1 for PM2 5 i...

Page 137: ...w point temperature in 0 01 C 6 for dew point temperature in 0 01 F AAHO Read humidity offset AAHO data Set humidity offset data in format of 100 00 100 00 AALO data CN Set low alarm limit of an AI ch...

Page 138: ...0 01 C 6 for dew point temperature in 0 01 F AARL Read all low latched values of analog input channels response CO in 1 ppm relative humidity in 0 01 temperature in 0 01 C temperature in 0 01 F dew p...

Page 139: ...host watchdog timeout status AA2 read host watchdog enable disable status and timeout value AA3ETT enable disable host watchdog and set timeout value E 0 disable host watchdog 1 enable host watchdog...

Page 140: ...ON protocol N 0 DCON 1 Modbus RTU AA2 Reads configuration AA is the RS 485 address hex AA5 Reads reset status response AA1 first after power on AA0 others AA Read All Analog Inputs response CO2 in 1 p...

Page 141: ...op bits N 8 2 10 even parity 1 stop bit E 8 1 11 odd parity 1 stop bit O 8 1 FF data format Bit 6 0 checksum disabled 1 checksum enabled AAABC Read status of the automatic baseline correction Response...

Page 142: ...n 0 01 3 for temperature in 0 01 C 4 for temperature in 0 01 F 5 for dew point temperature in 0 01 C 6 for dew point temperature in 0 01 F AACHCN Clear high latched alarm of a channel N 0 for CO2 In 1...

Page 143: ...1 C 6 for dew point temperature in 0 01 F AADI read DO response AA00O00 AADLB Read the beginning of the period setting of the data logger for period logging mode response AAyyyymmddhhmmss AADLByyyymmd...

Page 144: ...ing when full 1 overwrite AADLP Read the sampling period setting of the data logger response AAhhmmss hh hour 0 to 24 mm minute 0 to 59 ss second 0 to 59 AADLPhhmmss Set the sampling period setting of...

Page 145: ...CN Set high alarm limit of an AI channel N 0 for CO2 In 1ppm 1 for PM2 5 in 1 ug m3 2 for relative humidity in 0 01 3 for temperature in 0 01 C 4 for temperature in 0 01 F 5 for dew point temperature...

Page 146: ...01 F AARHCN Read high alarm limit of an AI channel N 0 for CO2 In 1ppm 1 for PM2 5 in 1 ug m3 2 for relative humidity in 0 01 3 for temperature in 0 01 C 4 for temperature in 0 01 F 5 for dew point t...

Page 147: ...offset in 0 01 C 100 00 100 00 clear host watchdog timeout counter AA0 read host watchdog status AA1 clear host watchdog timeout status AA2 read host watchdog enable disable status and timeout value A...

Page 148: ...DCON 1 Modbus RTU AA2 Reads configuration AA is the RS 485 address hex AA5 Reads reset status response AA1 first after power on AA0 others AA Read All Analog Inputs response CO in 1 ppm CO2 in 1 ppm...

Page 149: ...op bits N 8 2 10 even parity 1 stop bit E 8 1 11 odd parity 1 stop bit O 8 1 FF data format Bit 6 0 checksum disabled 1 checksum enabled AAABC Read status of the automatic baseline correction Response...

Page 150: ...for temperature in 0 01 C 5 for temperature in 0 01 F 6 for dew point temperature in 0 01 C 7 for dew point temperature in 0 01 F AACHCN Clear high latched alarm of a channel N 0 for CO In 1ppm 1 for...

Page 151: ...e in 0 01 C 7 for dew point temperature in 0 01 F AADI read DO response AA00O00 AADLB Read the beginning of the period setting of the data logger for period logging mode response AAyyyymmddhhmmss AADL...

Page 152: ...full 1 overwrite AADLP Read the sampling period setting of the data logger response AAhhmmss hh hour 0 to 24 mm minute 0 to 59 ss second 0 to 59 AADLPhhmmss Set the sampling period setting of the dat...

Page 153: ...gh alarm limit of an AI channel N 0 for CO In 1ppm 1 for CO2 In 1ppm 2 for PM2 5 in 1 ug m3 3 for relative humidity in 0 01 4 for temperature in 0 01 C 5 for temperature in 0 01 F 6 for dew point temp...

Page 154: ...RHCN Read high alarm limit of an AI channel N 0 for CO In 1ppm 1 for CO2 In 1ppm 2 for PM2 5 in 1 ug m3 3 for relative humidity in 0 01 4 for temperature in 0 01 C 5 for temperature in 0 01 F 6 for de...

Page 155: ...offset in 0 01 C 100 00 100 00 clear host watchdog timeout counter AA0 read host watchdog status AA1 clear host watchdog timeout status AA2 read host watchdog enable disable status and timeout value A...

Page 156: ...located in the company CD CD Napdos IIOT utility and needless to install http ftp icpdas com pub cd usbcd napdos iiot utility modbusmastertoolpc This section intends to guide the steps for creating th...

Page 157: ...e Connection menu 5 Select the communication interface When using TCP IP as the interface input the IP for your logger and click on the OK button When using RS 485 as the interface select the COM port...

Page 158: ...B ModbusMasterToolPC 158 6 Select Definition in the Setup menu 7 Select the Modbus function code input the start address and length and click on the OK button 8 Read data...

Page 159: ...9 Write data to Holding Register or Coil Status 1 Highlight the Modbus address in the Holding Register or Coil Status list 2 Select Set Value in the Setup menu 3 Input the data in the Value box and cl...

Page 160: ...of channel 1 to 5 channel 1 relative humidity in 0 01 channel 2 temperature in 0 01 C channel 3 temperature in 0 01 F channel 4 dew point temperature in 0 01 C channel 5 dew point temperature in 0 01...

Page 161: ...s RTU protocol R W 40492 RS 485 host watchdog timeout count write 0 to clear Only for Modbus RTU protocol R W 40497 Beep on alarm 0 disable 1 to 250 beep on alarm time in seconds 251 beep on alarm con...

Page 162: ...s full 0 no 1 yes R W 40878 Hour of the data logger sampling period 0 24 R W 40879 Minute of the data logger sampling period 0 59 R W 40880 Second of the data logger sampling period 0 59 R W 40881 Sta...

Page 163: ...host watch dog timeout status Only for Modbus RTU protocol R W 00273 Reset status 1 first read after powered on 0 not the first read after powered on Only for Modbus RTU protocol R 00280 Write 1 to cl...

Page 164: ...01 channel 2 temperature in 0 01 C channel 3 temperature in 0 01 F channel 4 dew point temperature in 0 01 C channel 5 dew point temperature in 0 01 F R W 40272 Modbus NetID Only for Modbus TCP proto...

Page 165: ...r Only for Modbus RTU protocol R W 40496 Automatic baseline correction for CO2 measurement 0 disable 1 enable R W 40497 Beep on alarm 0 disable 1 to 250 beep on alarm time in seconds 251 beep on alarm...

Page 166: ...s full 0 no 1 yes R W 40878 Hour of the data logger sampling period 0 24 R W 40879 Minute of the data logger sampling period 0 59 R W 40880 Second of the data logger sampling period 0 59 R W 40881 Sta...

Page 167: ...host watch dog timeout status Only for Modbus RTU protocol R W 00273 Reset status 1 first read after powered on 0 not the first read after powered on Only for Modbus RTU protocol R 00280 Write 1 to cl...

Page 168: ...ty in 0 01 channel 3 temperature in 0 01 C channel 4 temperature in 0 01 F channel 5 dew point temperature in 0 01 C channel 6 dew point temperature in 0 01 F R W 40272 Modbus NetID Only for Modbus TC...

Page 169: ...r Only for Modbus RTU protocol R W 40496 Automatic baseline correction for CO2 measurement 0 disable 1 enable R W 40497 Beep on alarm 0 disable 1 to 250 beep on alarm time in seconds 251 beep on alarm...

Page 170: ...s full 0 no 1 yes R W 40878 Hour of the data logger sampling period 0 24 R W 40879 Minute of the data logger sampling period 0 59 R W 40880 Second of the data logger sampling period 0 59 R W 40881 Sta...

Page 171: ...host watch dog timeout status Only for Modbus RTU protocol R W 00273 Reset status 1 first read after powered on 0 not the first read after powered on Only for Modbus RTU protocol R 00280 Write 1 to cl...

Page 172: ...nel 2 to 6 channel 2 relative humidity in 0 01 channel 3 temperature in 0 01 C channel 4 temperature in 0 01 F channel 5 dew point temperature in 0 01 C channel 6 dew point temperature in 0 01 F R W 4...

Page 173: ...s RTU protocol R W 40492 RS 485 host watchdog timeout count write 0 to clear Only for Modbus RTU protocol R W 40497 Beep on alarm 0 disable 1 to 250 beep on alarm time in seconds 251 beep on alarm con...

Page 174: ...s full 0 no 1 yes R W 40878 Hour of the data logger sampling period 0 24 R W 40879 Minute of the data logger sampling period 0 59 R W 40880 Second of the data logger sampling period 0 59 R W 40881 Sta...

Page 175: ...host watch dog timeout status Only for Modbus RTU protocol R W 00273 Reset status 1 first read after powered on 0 not the first read after powered on Only for Modbus RTU protocol R 00280 Write 1 to cl...

Page 176: ...01 channel 2 temperature in 0 01 C channel 3 temperature in 0 01 F channel 4 dew point temperature in 0 01 C channel 5 dew point temperature in 0 01 F R W 40272 Modbus NetID Only for Modbus TCP proto...

Page 177: ...t watchdog timeout count write 0 to clear Only for Modbus RTU protocol R W 40497 Beep on alarm 0 disable 1 to 250 beep on alarm time in seconds 251 beep on alarm continuously R W 30513 30518 40513 405...

Page 178: ...0878 Hour of the data logger sampling period 0 24 R W 40879 Minute of the data logger sampling period 0 59 R W 40880 Second of the data logger sampling period 0 59 R W 40881 Starting year when logging...

Page 179: ...ol W 00234 Write 1 to reboot module Only for Modbus TCP protocol W 00257 RS 485 Protocol 0 DCON 1 Modbus RTU Only for Modbus RTU protocol R W 00260 Modbus RTU host watchdog mode 0 same as I 7000 1 can...

Page 180: ...ite 1 to clear high latched alarm R W 00321 00326 Enable disable alarm of channel 0 to 5 R W 00337 00342 Alarm type momentary or latched of channel 0 to 5 R W 00385 00390 Write 1 to clear high latched...

Page 181: ...01 channel 2 temperature in 0 01 C channel 3 temperature in 0 01 F channel 4 dew point temperature in 0 01 C channel 5 dew point temperature in 0 01 F R W 40272 Modbus NetID Only for Modbus TCP proto...

Page 182: ...t watchdog timeout count write 0 to clear Only for Modbus RTU protocol R W 40497 Beep on alarm 0 disable 1 to 250 beep on alarm time in seconds 251 beep on alarm continuously R W 30513 30518 40513 405...

Page 183: ...0878 Hour of the data logger sampling period 0 24 R W 40879 Minute of the data logger sampling period 0 59 R W 40880 Second of the data logger sampling period 0 59 R W 40881 Starting year when logging...

Page 184: ...ol W 00234 Write 1 to reboot module Only for Modbus TCP protocol W 00257 RS 485 Protocol 0 DCON 1 Modbus RTU Only for Modbus RTU protocol R W 00260 Modbus RTU host watchdog mode 0 same as I 7000 1 can...

Page 185: ...annel 0 to 5 Write 1 to clear high latched alarm R W 00321 00326 Enable disable alarm of channel 0 to 5 R W 00337 00342 Alarm type momentary or latched of channel 0 to 5 R W 00385 00390 Write 1 to cle...

Page 186: ...0 01 channel 2 temperature in 0 01 C channel 3 temperature in 0 01 F channel 4 dew point temperature in 0 01 C channel 5 dew point temperature in 0 01 F R W 40272 Modbus NetID Only for Modbus TCP prot...

Page 187: ...t watchdog timeout count write 0 to clear Only for Modbus RTU protocol R W 40497 Beep on alarm 0 disable 1 to 250 beep on alarm time in seconds 251 beep on alarm continuously R W 30513 30518 40513 405...

Page 188: ...0878 Hour of the data logger sampling period 0 24 R W 40879 Minute of the data logger sampling period 0 59 R W 40880 Second of the data logger sampling period 0 59 R W 40881 Starting year when logging...

Page 189: ...ol W 00234 Write 1 to reboot module Only for Modbus TCP protocol W 00257 RS 485 Protocol 0 DCON 1 Modbus RTU Only for Modbus RTU protocol R W 00260 Modbus RTU host watchdog mode 0 same as I 7000 1 can...

Page 190: ...annel 0 to 5 Write 1 to clear high latched alarm R W 00321 00326 Enable disable alarm of channel 0 to 5 R W 00337 00342 Alarm type momentary or latched of channel 0 to 5 R W 00385 00390 Write 1 to cle...

Page 191: ...0 01 channel 2 temperature in 0 01 C channel 3 temperature in 0 01 F channel 4 dew point temperature in 0 01 C channel 5 dew point temperature in 0 01 F R W 40272 Modbus NetID Only for Modbus TCP prot...

Page 192: ...t watchdog timeout count write 0 to clear Only for Modbus RTU protocol R W 40497 Beep on alarm 0 disable 1 to 250 beep on alarm time in seconds 251 beep on alarm continuously R W 30513 30518 40513 405...

Page 193: ...0878 Hour of the data logger sampling period 0 24 R W 40879 Minute of the data logger sampling period 0 59 R W 40880 Second of the data logger sampling period 0 59 R W 40881 Starting year when logging...

Page 194: ...ol W 00234 Write 1 to reboot module Only for Modbus TCP protocol W 00257 RS 485 Protocol 0 DCON 1 Modbus RTU Only for Modbus RTU protocol R W 00260 Modbus RTU host watchdog mode 0 same as I 7000 1 can...

Page 195: ...annel 0 to 5 Write 1 to clear high latched alarm R W 00321 00326 Enable disable alarm of channel 0 to 5 R W 00337 00342 Alarm type momentary or latched of channel 0 to 5 R W 00385 00390 Write 1 to cle...

Page 196: ...n 0 01 channel 2 temperature in 0 01 C channel 3 temperature in 0 01 F channel 4 dew point temperature in 0 01 C channel 5 dew point temperature in 0 01 F R W 40272 Modbus NetID Only for Modbus TCP pr...

Page 197: ...t watchdog timeout count write 0 to clear Only for Modbus RTU protocol R W 40497 Beep on alarm 0 disable 1 to 250 beep on alarm time in seconds 251 beep on alarm continuously R W 30513 30518 40513 405...

Page 198: ...0878 Hour of the data logger sampling period 0 24 R W 40879 Minute of the data logger sampling period 0 59 R W 40880 Second of the data logger sampling period 0 59 R W 40881 Starting year when logging...

Page 199: ...ol W 00234 Write 1 to reboot module Only for Modbus TCP protocol W 00257 RS 485 Protocol 0 DCON 1 Modbus RTU Only for Modbus RTU protocol R W 00260 Modbus RTU host watchdog mode 0 same as I 7000 1 can...

Page 200: ...annel 0 to 5 Write 1 to clear high latched alarm R W 00321 00326 Enable disable alarm of channel 0 to 5 R W 00337 00342 Alarm type momentary or latched of channel 0 to 5 R W 00385 00390 Write 1 to cle...

Page 201: ...ture in 0 01 F channel 5 dew point temperature in 0 01 C channel 6 dew point temperature in 0 01 F R W 40235 40239 Low alarm limit of channel 2 to 6 channel 2 relative humidity in 0 01 channel 3 tempe...

Page 202: ...400 57600 115200 Bits 7 6 00 no parity 1 stop bit N 8 1 01 no parity 2 stop bits N 8 2 10 even parity 1 stop bit E 8 1 11 odd parity 1 stop bit O 8 1 R W 40488 RS 485 response delay time in ms valid r...

Page 203: ...30560 40560 Module name 0x0213 Only for Modbus TCP protocol R 40564 TCP disconnection timeout value 5 to 65535 in second 0 to disable Only for Modbus TCP protocol R W 40565 Module reset timeout value...

Page 204: ...eriod mode 0 to 23 R W 40891 Ending minute when logging in period mode 0 to 59 R W 40892 Ending second when logging in period mode 0 to 59 R W 40929 The first fan off period in a day beginning hour 0...

Page 205: ...f 1 on R W 00280 Write 1 to clear all high latched analog input values W 00281 Write 1 to clear all low latched analog input values W 00291 00295 Low alarm status of channel 2 to 6 Write 1 to clear lo...

Page 206: ...1 channel 3 temperature in 0 01 C channel 4 temperature in 0 01 F channel 5 dew point temperature in 0 01 C channel 6 dew point temperature in 0 01 F R W 00385 00391 Write 1 to clear high latched anal...

Page 207: ...ture in 0 01 F channel 5 dew point temperature in 0 01 C channel 6 dew point temperature in 0 01 F R W 40235 40239 Low alarm limit of channel 2 to 6 channel 2 relative humidity in 0 01 channel 3 tempe...

Page 208: ...400 57600 115200 Bits 7 6 00 no parity 1 stop bit N 8 1 01 no parity 2 stop bits N 8 2 10 even parity 1 stop bit E 8 1 11 odd parity 1 stop bit O 8 1 R W 40488 RS 485 response delay time in ms valid r...

Page 209: ...30560 40560 Module name 0x0213 Only for Modbus TCP protocol R 40564 TCP disconnection timeout value 5 to 65535 in second 0 to disable Only for Modbus TCP protocol R W 40565 Module reset timeout value...

Page 210: ...eriod mode 0 to 23 R W 40891 Ending minute when logging in period mode 0 to 59 R W 40892 Ending second when logging in period mode 0 to 59 R W 40929 The first fan off period in a day beginning hour 0...

Page 211: ...n control 0 off 1 on R W 00280 Write 1 to clear all high latched analog input values W 00281 Write 1 to clear all low latched analog input values W 00291 00295 Low alarm status of channel 2 to 6 Write...

Page 212: ...annel 3 temperature in 0 01 C channel 4 temperature in 0 01 F channel 5 dew point temperature in 0 01 C channel 6 dew point temperature in 0 01 F R W 00385 00391 Write 1 to clear high latched analog i...

Page 213: ...lative humidity in 0 01 channel 4 temperature in 0 01 C channel 5 temperature in 0 01 F channel 6 dew point temperature in 0 01 C channel 7 dew point temperature in 0 01 F R W 40236 40240 Low alarm li...

Page 214: ...1 to 247 R W 40486 RS 485 baud rate and parity settings Bits 5 0 Baud rate valid range 3 10 Code 0x03 0x04 0x05 0x06 Baud 1200 2400 4800 9600 Code 0x07 0x08 0x09 0x0A Baud 19200 38400 57600 115200 Bi...

Page 215: ...re in 0 01 C channel 5 temperature in 0 01 F channel 6 dew point temperature in 0 01 C channel 7 dew point temperature in 0 01 F R 30556 40556 Module reset status 1 power on 2 watchdog 3 software rese...

Page 216: ...date when logging in period mode 1 to 31 R W 40884 Starting hour when logging in period mode 0 to 23 R W 40885 Starting minute when logging in period mode 0 to 59 R W 40886 Starting second when loggi...

Page 217: ...ar host watchdog timeout status R W 00261 RS 485 host watchdog mode 1 enable 0 disable R W 00262 Write 1 to play notification sound Only for CL 213 E W 00270 Host watch dog timeout status write 1 to c...

Page 218: ...disable alarm write 1 to enable alarm channel 0 CO in 1ppm channel 1 CO2 in 1ppm channel 2 PM2 5 in 1ug m3 channel 3 relative humidity in 0 01 channel 4 temperature in 0 01 C channel 5 temperature in...

Page 219: ...l 5 temperature in 0 01 F channel 6 dew point temperature in 0 01 C channel 7 dew point temperature in 0 01 F W 00417 00424 Write 1 to clear low latched analog input value of channel 0 to 7 channel 0...

Page 220: ...85 Start IP address of the allocated IP by the DHCP server in AP mode R W 40687 IP address type in station mode 0 for static type 1 for DHCP R W 40688 40689 Device IP address R W 40690 40691 Device su...

Page 221: ...ased 1 1 0 2018 Feb Added CL 201 E CL 202 E CL 203 E information Modified the path for software and manual in the CD and on the website 1 2 0 2019 Apr AddedCL 211 CL 212 CL 213 CL 204 E CL 205 E CL 20...

Reviews: