A-3. CL-203-E DCON Command Sets
- 101 -
Command
Description
@AATO
Read temperature offset in 0.01°C
@AATO(data)
Set temperature offset in 0.01°C, -100.00 ~ +100.00
~**
clear host watchdog timeout counter
~AA0
read host watchdog status
~AA1
clear host watchdog timeout status
~AA2
read host watchdog enable/disable status and timeout value
~AA3ETT
enable/disable host watchdog and set timeout value
E-> 0: disable host watchdog, 1: enable host watchdog
TT: host watchdog timeout in 0.1s in hex format
~AA4
read DO power on and safe value
~AA50P0S
set DO power on and safe value
P-> 0: power on value off, 1: power on value on
S-> 0: safe value off, 1: safe value on
~AARD
read response delay time in ms in hex format
~AARDVV
set response delay time in ms, VV in hex format, 00 - 1E