INIT
In case of the following situations, users have to set the pin 4.INIT on SW1 in the ON
position and power-cycle the CL-200 module:
- Change protocol from PC
- Change DCON configuration such as baudrate, parity and checksum
- Communication failure with a CL-200 module.
When a CL-200 module is powered-on with the pin 4.INIT in ON position, the protocol is
DCON, address is 0, Baud Rate is 9600 bps, Parity is set to N/8/1 and Checksum is
disabled.
After configuring the communication parameters, click the
Set Module Configurations
button, set the INIT to OFF position and power-cycle the CL-200 to take the settings
effect.
Note
The INIT switch does not need to be set in the ON position when changing the
address, baudrate and parity for ModbusRTU communication; users only have to
power-cycle the module after complete configuration.