A-12. CL-213 / CL-213-E DCON Command Sets
- 149 -
Command
Description
%AANNTTCCFF
Sets configuration,
AA: current address
NN: new address,
TT = 00,
CC: new baud rate
Bits 5:0
Baud rate, 0x03 ~ 0x0A
Code
0x03
0x04
0x05
0x06
Baud
1200
2400
4800
9600
Code
0x07
0x08
0x09
0x0A
Baud
19200
38400
57600
115200
Bits 7:6
00: no parity, 1 stop bit (N,8,1)
01: no parity, 2 stop bits (N,8,2)
10: even parity, 1 stop bit (E,8,1)
11: odd parity, 1 stop bit (O,8,1)
FF: data format
Bit 6
0: checksum disabled
1: checksum enabled
@AAABC
Read status of the automatic baseline correction
Response
!AAN, N=0: disabled, 1: enabled
@AAABCN
Set the automatic baseline correction
N->0: disabled, 1:enabled
@AABA
Read beep on alarm time
response
!AAHH, HH in hex, 0: disabled, 1 ~ 250: beep on alarm time in
seconds, 251: beep on alarm continuously
@AABAHH
Set beep on alarm, HH in hex,
0: disabled,
1 ~ 250: beep on alarm time in seconds,
251: beep on alarm continuously