A-12. CL-213 / CL-213-E DCON Command Sets
- 152 -
Command
Description
@AADLEyyyymmd
dhhmmss
Set the ending of the period setting of the data logger for period
logging mode
yyyy: year, 2000 to 2199, mm: month, 01 to 12, dd: date, 01 to 31,
hh: hour, 0 to 24, mm: minute, 0 to 59, ss: second, 0 to 59
@AADLN
Read number of log records in the data logger
response
!AAhhhhhhhh, hhhhhhhh in hex format
@AADLO
Read the overwriting mode when data logger is full
response
!AAh, 0: stop logging when full, 1: overwrite
@AADLOh
Set the overwriting mode when data logger is full
h->0: stop logging when full, 1: overwrite
@AADLP
Read the sampling period setting of the data logger
response
!AAhhmmss, hh: hour, 0 to 24, mm: minute, 0 to 59, ss: second,
0 to 59
@AADLPhhmmss Set the sampling period setting of the data logger
@AADLS
Read logging status of the data logger
response
!AAhh, hh in hex format, 00: stopped, 01: running, others: error
@AADO0V
set DO, V-> 0: off, 1: on
@AAEATCN
Enable AI alarm of a channel,
N = 0 for CO
In 1ppm,
1 for CO
2
In 1ppm,
2 for PM2.5 in 1 ug/m3,
3 for relative humidity in 0.01%,
4 for temperature in 0.01°C,
5 for temperature in 0.01°F,
6 for dew point temperature in 0.01°C,
7 for dew point temperature in 0.01°F
T->M: momentary alarm mode, L: latched alarm mode
@AAFN
Read fan status
Response
!AAE, E=0: fan off, 1: fan on,
@AAFNE
Turn fan on or off
E=0: fan off, 1: fan on