A-10. CL-211 / CL-211-E DCON Command Sets
- 137 -
Command
Description
@AAFNPibhbmeh
em
Set the i-th fan off period in a day, i = 0 to 5, bh: beginning hour, 0 to
23, bm: beginning minute, 0 to 59, eh: ending hour, 0 to 23, em:
ending minute, 0 to 59. The beginning hour/minute should be
earlier than the ending hour/minute. Otherwise, the setting is
ignored. If all of the six period settings are invalid, then the fan is
controlled by the @AAFNE command.
@AAHI(data)CN
Set high alarm limit of an AI channel,
N = 0 for CO
In 1ppm,
1 for PM2.5 in 1 ug/m3,
2 for relative humidity in 0.01%,
3 for temperature in 0.01°C,
4 for temperature in 0.01°F,
5 for dew point temperature in 0.01°C,
6 for dew point temperature in 0.01°F
@AAHO
Read humidity offset
@AAHO(data)
Set humidity offset, data in format of -100.00 ~ +100.00
@AALO(data)CN Set low alarm limit of an AI channel,
N = 1 for relative humidity in 0.01%,
2 for temperature in 0.01°C,
3 for temperature in 0.01°F,
4 for dew point temperature in 0.01°C,
5 for dew point temperature in 0.01°F
@AAPO
Read PM2.5 offset
@AAPO(data)
Set PM2.5 offset, data in format of -00100. ~ +00100.
@AARACN
Read AI alarm enabled/disabled status of a channel
response
!AAN, N->0: disabled, 1: momentary, 2: latched
@AARAO
Read AI alarm status
response
!AAHHLL
@AARH
Read all high latched values of analog input channels
response
>(CO in 1 ppm)(relative humidity in 0.01%)(temperature in
0.01°C)(temperature in 0.01°F)(dew point temperature in
0.01°C)(dew point temperature in 0.01°F)