8.4.3 Supported
Object
Details
Binary Input Objects
BI1 ........ Indicates whether the inverter is running forward. Corresponds to function code M14, bit 0.
BI2 ........ Indicates whether the inverter is running reverse. Corresponds to function code M14, bit 1.
BI3 ........ Indicates DC injection braking or pre-exciting. Corresponds to function code M14, bit 2.
BI4 ........ Indicates inverter shutdown. Corresponds to function code M14, bit 3.
BI5 ........ Indicates braking. Corresponds to function code M14, bit 4.
BI6 ........ Indicates normal DC bus voltage. Corresponds to function code M14, bit 5.
BI7 ........ Indicates torque limited. Corresponds to function code M14, bit 6.
BI8 ........ Indicates voltage limited. Corresponds to function code M14, bit 7.
BI9 ........ Indicates current limited. Corresponds to function code M14, bit 8.
BI10 ...... Indicates acceleration. Corresponds to function code M14, bit 9.
BI11 ...... Indicates deceleration. Corresponds to function code M14, bit 10.
BI12 ...... Indicates alarm. Corresponds to function code M14, bit 11.
BI13 ...... Indicates communications established. Corresponds to function code M14, bit 12.
BI14 ...... Indicates function code write in progress. Corresponds to function code M14, bit 15.
Binary Output Objects
BO1 ...... Forward command. Corresponds to function code S06, bit 0.
BO2 ...... Reverse command. Corresponds to function code S06, bit 1.
BO3 ...... X1 command. Corresponds to function code S06, bit 2.
BO4 ...... X2 command. Corresponds to function code S06, bit 3.
BO5 ...... X3 command. Corresponds to function code S06, bit 4.
BO6 ...... X4 command. Corresponds to function code S06, bit 5.
BO7 ...... X5 command. Corresponds to function code S06, bit 6.
BO8 ...... X6 command. Corresponds to function code S06, bit 7.
BO9 ...... X7 command. Corresponds to function code S06, bit 8.
BO10 .... X8 command. Corresponds to function code S06, bit 9.
BO11 .... X9 command. Corresponds to function code S06, bit 10.
BO12 .... EN terminal command. Corresponds to function code S06, bit 11.
BO13 .... XF (FWD) command. Corresponds to function code S06, bit 13.
BO14 .... XR (REV) command. Corresponds to function code S06, bit 14.
BO15 .... Activates the alarm reset. Corresponds to function code S06, bit 15.
Analog Input Objects
AI1 ........ The output frequency of the inverter in 0.01 Hertz units (6000=60.00Hz). Corresponds to
function code M09.
AI2 ........ The output current of the inverter in 0.1 or 0.01 Amp units (depends on inverter capacity).
Corresponds to function code W05.
AI3 ........ The output voltage of the inverter in 0.1 Volt units (1000=100.0V). Corresponds to function
code W06.
AI4 ........ Input power of the inverter in 0.01 kW units. Corresponds to function code W21.
AI5 ........ Output power of the inverter in 0.01 kW units. Corresponds to function code W22.
Analog Output Objects
AO1 ...... Frequency command of the inverter in 0.01 Hertz units. Corresponds to function code S05.
AO2 ...... Sets the acceleration time in 0.1 second units. Corresponds to function code S08.
AO3 ...... Sets the deceleration time in 0.1 second units. Corresponds to function code S09.