ICC
29
5.4.2 Function Code Group Selection List
The Function Code Group
Selection List is located in the
upper-left hand corner of the
Monitor Tab. Refer to Figure
22. Individual groups can be
selected by clicking on the
group name. Multiple groups
may also be selected by holding
down the CTRL key while
clicking on the group names, or
a range of groups can be
selected by first selecting the
starting group, and then holding
down the SHIFT key while
selecting the last group in the
range. When a function code group is selected, the function codes contained in that group are displayed
in the Function Code List (refer to section 5.4.3). The following function code groups are available:
All:
All function codes/registers are available.
Fundamental Functions:
F function codes are available.
Extension Terminal Functions:
E function codes are available.
Control Functions:
C function codes are available.
Motor 1 Parameters:
P function codes are available.
High Performance Functions:
H function codes are available.
Motor 2 Parameters:
A function codes are available.
Command Data:
S function codes are available.
Monitor Data 1:
M function codes are available.
Application Functions:
J function codes are available.
Link Functions:
Y function codes are available.
Monitor Data 2:
W function codes are available.
Alarm Data 1:
X function codes are available.
Alarm Data 2:
Z function codes are available.
Note that only the Command Data (S), Monitor Data 1 (M) and Monitor Data 2 (W) function code groups
are scanned, and that all others are non-scanned. The values of non-scanned function codes are not
continuously updated from the inverter. For more information regarding scanned vs. non-scanned
function codes, refer to sections 5.4.5 and 6.2.
5.4.3 Function Code List
The bottom half of the Monitor tab contains the function code list (refer to Figure 23). The function
codes that are displayed in the list at any given time depend on the function code groups that are
currently selected (refer to section 5.4.2), as well as whether or not any filters have been applied (refer
to section 5.4.4).
The first column of the Function Code List shows the inverter function code designation that is normally
used when accessing a given function code via the inverter’s keypad. Note that this column is for user
convenience and inverter user’s manual cross-reference only: function codes are not referenced through
the interface card by their function code designations, but by their register numbers.
The second column of the Function Code List shows the register number that provides network access
to each function code (refer to section 6). The third column contains the function code descriptions,
which are used by the filter function. The last column performs two functions: it displays the current
value of the function code, and (for writable function codes) also allows changing the function code’s
value by clicking on the number in the value column and entering the new value.
Figure 22: Function Code Group Selection List