background image

 

 

                                                                                                                                                                           p. 24 / 39

 

 

M21 – COUNTERS 
(CNTn, n=1…8) 

UoM 

Default 

Range 

 

 

 

 

 

P21.n.01 

Count source 

 

OFF 

OFF-ON-INPx-OUTx-LIMx-

REMx 

P21.n.02 

Channel number (x) 

 

1-8 

P21.n.03 

Multiplier 

 

1-1000 

P21.n.04 

Divisor 

 

1-1000 

P21.n.05 

Description of the counter 

 

CNTn 

(Text – 16 characters) 

P21.n.06 

Unit of measurement 

 

Umn 

(Text – 6 characters) 

P21.n.07 

Reset source 

 

OFF 

OFF-ON-INPx-OUTx-LIMx-

REMx 

P21.n.08 

Channel number (x) 

 

1-8 

Note: this menu is divided into 8 sections for counters CNT1..8 

P21.n.01 

- Signal that increments the count (on the output side). This may be the start-up of the 

DCRG8 (ON), when a threshold is exceeded (LIMx), an external input is enabled 
(INPx), etc. 

P21.n.02 

- Channel number x with reference to the previous parameter.

 

P21.n.03 

- Multiplier K. The counted pulses are multiplied by this value before being displayed.

 

P21.n.04 

- Divisional K. The counted pulses are divided by this value before being displayed. If 

other than 1, the counter is displayed with 2 decimal points.

 

P21.n.05 

- Counter description. 16-character free text.

 

P21.n.06 

- Counter unit of measurement. 6-character free text.

 

P21.n.07 

- Signal that resets the count. As long as this signal is enabled, the count remains 

zero.

 

P21.n.08 

- Channel number x with reference to the previous parameter.

 

 

 

   

 

M21 – COUNTERS

 

(CNTn, n=1…8) 

Ед. 

изм.

 

  

По ум.

 

  

Диапазон

 

 

 

 

 

 

P21.n.01

 

Источник отсчета 

 

ВЫКЛ. 

  ВЫКЛ.-ВКЛ.-INPx-OUTx-

LIMx-REMx 

P21.n.02

 

Номер канала (x) 

 

  1-8 

P21.n.03

 

Множитель 

 

  1-1000 

P21.n.04

 

Делитель 

 

  1-1000 

P21.n.05

 

Описание счетчика 

 

CNTn 

(Текст – 16 символов) 

P21.n.06

 

Единица измерения 

 

Ед. изм. 

(Текст – 6 символов) 

P21.n.07

 

Источник сброса 

 

ВЫКЛ. 

  ВЫКЛ.-ВКЛ.-INPx-OUTx-

LIMx-REMx 

P21.n.08

 

Номер канала (x) 

 

  1-8 

Примечание. Это меню состоит из 8 частей для счетчиков CNT1..8. 

P21.n.01 

– Сигнал, по которому значение счетчика увеличивается на единицу (на стороне 

выхода). Это может быть запуск устройства DCRG8 (ВКЛ.) при превышении 
порога (LIMx), включении внешнего входа (INPx) т.д. 

P21.n.02 

– Номер канала x с учетом предыдущего параметра.

 

P21.n.03 

– Множитель K. Отсчитанные импульсы умножаются на это значение перед 

отображением.

 

P21.n.04 

– Делитель K. Отсчитанные импульсы делятся на это значение перед 

отображением. Если значение не 1, то значение счетчика отображается с 2 
десятичными знаками.

 

P21.n.05 

– Описание счетчика. Произвольный текст длиной 16 символов.

 

P21.n.06 

– Единица измерения счетчика. Произвольный текст длиной 6 символов.

 

P21.n.07 

– Сигнал, сбрасывающий счетчик. Пока сигнал действует, значение счетчика 

остается 0.

 

P21.n.08 

– Номер канала x с учетом предыдущего параметра.

 

 

 

 

M22 - ANALOG INPUTS 
(AINn, n=1…4) 

UoM 

Default 

Range 

P22.n.01 

Input type 

 

OFF 

OFF 

0..20mA 

4….20mA 

0…10V 

-5V…+5V 

PT100 

P22.n.02 

Start of scale value 

 

-9999 - +9999 

P22.n.03 

Multiplier 

 

x1 

/100 – x1k 

P22.n.04 

End of scale value 

 

-9999 - +9999 

P22.n.05 

Multiplier 

 

x1 

/100 – x1k 

P22.n.06 

Description  

 

AINn 

(Testo – 16 caratteri) 

P22.n.07 

Unit of measurement 

 

UMn 

(Testo – 6 caratteri) 

Note: this menu is divided into 4 sections for the analog inputs AIN1…AIN4, available 
with the EXP1004 expansion modules. 

P22.n.01

 - Specifies the type of sensor connected to analog input. The sensor should be 

connected to the appropriate terminal for the type selected. See input module manual. 

P22.n.02 and P22.n.03 

- Define the value to display for a min. sensor signal, in other words at 

the start of the range defined by the type (0mA, 4mA, 0V, -5V, etc.). Note: these 
parameters aren't used for a type PT100 sensor. 

P22.n.04 and P22.n.05 

- Define the value to display for a max. sensor signal, in other words at 

the end of scale of the range defined by the type (20ma, 10V, +5V, etc.). These 
parameters aren't used for a type PT100 sensor. 

P22.n.06 

- Description of measurements associated with analog input. 16-character free text. 

P22.n.07 

- Unit of measurement. 6-character free text. If the input is type PT100 and the text of 

the unit of measurement is 

°F

, the temperature will be displayed in degrees 

Fahrenheit, otherwise it will be in degrees Celsius. 

 

 

Example of application: The analog input AIN3 must read a 4…20mA signal from an electronic 

level sensor, that will have to be shown on the display with the descriprion ‘Reserve fuel tank 
level’, with a full scale of 1500 litres. 

So, we must program section 3 of this menu, that is referred to AIN3. 
P22.3.01 = 4…20mA 
P22.3.02 = 0 

 

P22.3.03 = x1 

 

 

P22.3.04 = 1500 

 

P22.3.05 = x1

 

 

P22.3.06 = ‘Reserve tank level’ 
P22.3.07 =’ litres’ 

 

 
 

   

 

M22 - ANALOG INPUTS

 

(AINn, n=1…4) 

Ед. 

изм.

 

  

По ум.

 

  

Диапазон

 

P22.n.01

 

Тип входа 

 

ВЫКЛ. 

ВЫКЛ. 

0..20 мА 

4….20 мА 

0…10 В 

-5 В…+5 В 

PT100 

P22.n.02

 

Начальное значение 
шкалы 

 

  -9999 - +9999 

P22.n.03

 

Множитель 

 

x1 

/100 – x1k 

P22.n.04

 

Конечное значение шкалы 

 

  -9999 - +9999 

P22.n.05

 

Множитель 

 

x1 

/100 – x1k 

P22.n.06

 

Описание  

 

AINn 

  (Текст – 16 символов) 

P22.n.07

 

Единица измерения 

 

Ед. изм. 

  (Текст – 6 символов) 

Примечание. Это меню состоит из 4 частей для аналоговых входов AIN1…AIN4, 
доступных с модулями расширения EXP1004. 

P22.n.01

 – Определяет тип датчика, подключенного к аналоговому входу. Датчик должен 

быть подключен к соответствующему контакту выбранного типа. См. руководство 

к модулю входов. 

P22.n.02 и P22.n.03 

– Определяют значение, отображаемое для мин. сигнала датчика, то 

есть, в конце диапазона, определенного типом (0 мА, 4 мА, 0 В, -5 В и т.д.). 
Примечание. Эти параметры не используются для датчика типа PT100. 

P22.n.04 и P22.n.05 

– Определяют значение, отображаемое для макс. сигнала датчика, 

то есть, в конце шкалы диапазона, определенного типом (20 мА, 10 В, +5 В и 
т.д.). Эти параметры не используются для датчика типа PT100. 

P22.n.06 

– Описание измерений, связанных с аналоговым входом. Произвольный текст 

длиной 16 символов. 

P22.n.07 

– Единица измерения. Произвольный текст длиной 6 символов. Если вход типа 

PT100 и текст единицы измерения – 

°F

, то температура отображается в градусах 

Фаренгейта, иначе – в градусам Цельсия. 

 

 

Пример  применения:

 

Аналоговый  вход  AIN3  должен  считывать  сигнал  4…20 мА  от 

электронного  уровнемера,  который  нужно  будет  выводить  на  дисплей  с  описанием 
«Reserve  fuel  tank  level»  (Уровень  в  резервном  топливном  баке)  при  полной  шкале  на 
1500 литров.

 

Итак, необходимо задать параметры в разделе 3 этого меню, то есть AIN3.

 

P22.3.01 = 4…20 мА 
P22.3.02 = 0

 

 

P22.3.03 = x1

  

 

P22.3.04 = 1500

 

 

P22.3.05 = x1

 

 

P22.3.06 = ‘Reserve tank level’

 

P22.3.07 =’ litres’

 

 

 

 

M23 – ANALOG OUTPUTS  
(AOUn, n=1…4) 

UoM 

Default 

Range 

P23.n.01 

Output type 

 

OFF 

OFF 

0..20mA 

4….20mA 

0…10V 

-5V…+5V 

P23.n.02 

Reference measurement 

 

OFF 

OFF- (misure) 

P23.n.03 

Channel number (x) 

 

OFF / 1-99 

P23.n.04 

Start of scale value 

 

-9999 - +9999 

P23.n.05 

Multiplier 

 

x1 

/100 – x10k 

P23.n.06 

End of scale value 

 

-9999 - +9999 

P23.n.07 

Multiplier 

 

x1 

/100 – x10k 

   

 

M23 – ANALOG OUTPUTS

  

(AOUn, n=1…4) 

Ед. 

изм.

 

  

По ум.

 

  

Диапазон

 

P23.n.01

 

Тип выхода 

 

ВЫКЛ. 

ВЫКЛ. 

0..20 мА 

4….20 мА 

0…10 В 

-5 В…+5 В 

P23.n.02

 

Контрольное измерение 

 

ВЫКЛ. 

  ВЫКЛ. (измерение) 

P23.n.03

 

Номер канала (x) 

 

ВЫКЛ. / 1-99 

P23.n.04

 

Начальное значение 
шкалы 

 

  -9999 - +9999 

P23.n.05

 

Множитель 

 

x1 

/100 – x10k 

P23.n.06

 

Конечное значение шкалы 

 

  -9999 - +9999 

P23.n.07 

Множитель 

 

x1 

/100 – x10k 

ЧП

 «

Профиэлектро

» 

Т

. +380 44 361-62-55, 80 

e-mail: [email protected] 

www. profielectro.net.ua 

Summary of Contents for RPC 8BGA

Page 1: ...Main menu 4 Password access 4 Display page navigation 5 Table of display pages 5 Harmonic analysis page 7 Waveform pages 7 Expandability 8 Additional resources 9 Communication channels 9 Inputs output...

Page 2: ...y outputs o Additional analog I O for PT100 temperature current voltage Capability to operate with several units interconnected in Master Slave mode o Maximum configuration Master 8 slave o Max 32 ste...

Page 3: ...t the step is not available because its reconnection time is not yet exhausted In this case sending a command to close the step number will flash to indicate that the operation has been confirmed and...

Page 4: ...d and the access is free If instead the passwords have been enabled and defined then to get access it is necessary to enter the password first specifying the numeric code through the keypad To enable...

Page 5: ...o the display remains were it was last You can set this function in menu M01 Utility M01 Utility Table of display pages PAGES EXAMPLE Home page Power Voltage and current Step life statistics Temperatu...

Page 6: ...function is disabled For example if the limit function is not programmed the corresponding page won t be shown Event time stamp Event description Event number total Key switches between Total Partial...

Page 7: ...eric format selecting the required order through and The lower part of the screen will display a little arrow that points to the selected column and the relative percentage value of the three phases T...

Page 8: ...figuration will be saved and will become effective otherwise the mismatch will be shown at every subsequent power on of the system The present system configuration is shown in the dedicated page of th...

Page 9: ...hernet RS485 DCRG RS 485 Ethernet DCRG Ethernet COM1 COM2 COM3 Gateway DCRG Gateway Inputs outputs internal variables counters analog inputs The inputs and outputs are identified by a code and a seque...

Page 10: ...is less than the Lower threshold for the programmed delay When the measured value becomes higher than the upper setpoint after the set delay the LIM status is reset Max function the upper threshold de...

Page 11: ...protections like panel or capacitor overtemperature no voltage release harmonic protections etc The maximum possible configuration is one master with 8 slaves Example 1 application in series It is req...

Page 12: ...gical step and pairing step between logical and physical outputs of the master and the slave The program is then automatically extended to the slaves On the slave it is only necessary to set the slave...

Page 13: ...8 guaranteeing the greatest safety for the operator o High speed data transfer o IP54 front panel o Limits the possibility of unauthorized access with device config Simply hold the CX dongle up to the...

Page 14: ...e panel M18 HARMONIC PROT Harmonic protections EXP1016 module M19 MISCELLANEOUS Various settings M20 LIMIT THRESHOLDS Limit thresholds on measurements M21 COUNTERS Generic programmable counters M22 AN...

Page 15: ...to go back to the parameter selection The entered value is stored Press to save all the settings and to quit the setup menu The controller executes a reset and returns to normal operation If the user...

Page 16: ...estore delay when no key pressed If set to OFF the display will always show the last page selected manually P01 08 Default page displayed on power up and after delay P01 09 Free text with alphanumeric...

Page 17: ...number of the step on the main page is shown in light gray P02 11 Connection sensitivity This parameter sets the speed of reaction of the controller With small values of P02 11 regulation is fast more...

Page 18: ...ws to avoid regulation oscillations Set this value according to the technical characteristics closing time declared by the manufacturer of the static contactor P02 30 Enables the setting of the setpoi...

Page 19: ...the previous parameter Example If the output function is set to Alarm Axx and you want this output to be energized for alarm A31 then P04 n 02 should be set to value 31 P04 n 3 Sets the state of the...

Page 20: ...4 PROGRAMMABLE INPUTS INPn n 1 8 UdM Default Range P14 n 01 INPn input function various see Input functions table P14 n 02 Function index x OFF OFF 1 99 P14 n 03 Contact type NO NO NC P14 n 04 Delay O...

Page 21: ...U Modbus ASCII Modbus TCP P16 n 06 IP address 192 168 1 1 000 000 000 000 255 255 255 255 P16 n 07 Subnet mask 255 255 255 0 000 000 000 000 255 255 255 255 P16 n 08 IP port 1001 0 9999 Note this menu...

Page 22: ...milar P17 08 Trip threshold for the capacitors overload protection alarm A08 that will arise after a integral delay time inversely proportional to the value of the overload P17 09 Threshold beyond whi...

Page 23: ...100 P18 n 08 5 1 100 P18 n 09 7 1 100 P18 n 10 11 1 100 P18 n 11 13 1 100 P18 n 12 1 55 0 212 P18 n 13 2 55 0 212 EXP1016 P18 n 01 P18 n 02 P18 n 03 2 1 P18 n 04 P18 n 05 P18 n 06 A11 P18 n 07 A12 P18...

Page 24: ...ould be connected to the appropriate terminal for the type selected See input module manual P22 n 02 and P22 n 03 Define the value to display for a min sensor signal in other words at the start of the...

Page 25: ...Active energy Kvarh Reactive energy kVA Apparent energy P24 n 02 The quantity of energy which must accumulate for a pulse to be emitted for example 10Wh 100Wh 1kWh etc P24 n 03 Pulse duration Applicat...

Page 26: ...function P26 n 10 Modem call A modem is connected as configured in setup P26 n 11 No LCD The alarm is managed normally but not shown on the display P26 n 12 13 Delay time Time delay in minutes or sec...

Page 27: ...eshold set with P18 n 11 A17 Harmonic protection Module nr n Temperature 1 too high The temperature 1 measured by the harmonic protection module is higher than threshold set with P18 n 12 A18 Harmonic...

Page 28: ...LOC 10 A19 LEN GEN 0 UAx GEN 0 Input function table The following table shows all the functions that can be attributed to the INPn programmable digital inputs Each input can be set for an reverse fun...

Page 29: ...Energised when global alarm 2 is active Global alarm 3 Energised when global alarm 3 is active Fan Panel ventilation fan Manual mode Active when the regulator is in MAN mode Automatic mode Active when...

Page 30: ...Senphi L3 26 W TOT Total active power 27 var TOT Total reactive power 28 VA TOT Total apparent power 29 Cosphi TOT Cosphi balanced three phase system 30 Senphi TOT Senphi balanced three phase system...

Page 31: ...he backup of user settings Once the required command has been selected press to execute it The device will prompt for a confirmation Pressing again the command will be executed To cancel the command e...

Page 32: ...arameter setting P02 03 Three phase P02 04 L3 P02 06 L1 L2 P02 22 LV P02 03 P02 04 L3 P02 06 L1 L2 P02 22 Single phase wiring SINGLE PHASE CONNECTION Voltage measure 1 phase voltage reading L1 N 1 L1...

Page 33: ...2 22 FULL THREE PHASE CONNECTION WITH NEUTRAL Wiring configuration used for standard applications with full three phase voltage control Voltage measure 3 ph to n and 3 ph to ph voltage readings L1 N L...

Page 34: ...V P02 23 ON P02 03 P02 04 L3 P02 06 L1 L2 P02 22 P02 23 Configuration with MV measurement and correction Voltage measure 3 ph to ph voltage reading L1 L2 L2 L3 L3 L1 on MV side 3 L1 L2 L2 L3 L3 L1 Cur...

Page 35: ...0 90 Capacitor overload current measure 3 Readings on L1 L2 L2 L3 L3 L1 3 L1 L2 L2 L3 L3 L1 Parameter setting P02 03 Three phase P02 04 L1 L2 L3 P02 06 L1 L2 L3 P02 22 LV P02 29 Fast P02 03 P02 04 L1...

Page 36: ...01 Stepx P07 1 01 Stepx P08 1 02 Stepx P05 01 COM1 P05 02 Slave01 P05 01 COM1 P05 02 Slave02 P05 01 COM1 P05 02 Slave03 P05 01 COM1 P05 02 P05 03 P05 04 P05 05 P04 1 01 x P06 1 01 x P07 1 01 x P08 1 0...

Page 37: ...morsetti OUT 1 600V 50 60 Hz OUT 2 OUT 3 OUT 4 OUT 5 OUT 6 OUT 7 OUT 8 SLOT 1 SLOT 2 SLOT 3 SLOT 4 Dimensioni meccaniche e foratura pannello mm 380 44 361 62 55 80 e mail info profielectro net ua www...

Page 38: ...age 415V 415 Rated current AC1 5A 250V AC15 1 5A 415V AC1 5A 250 AC15 1 5A 415 Real time clock Energy storage Back up capacitors Operating time without supply voltage About 12 15 days 12 15 Insulation...

Page 39: ...phase neutral voltage 300V 300 Rev Date Notes 00 30 10 2012 First release 00 30 10 2012 01 28 01 2013 Added Tanfi parameters P02 30 e P02 31 01 28 01 2013 tanfi P02 30 P02 31 380 44 361 62 55 80 e ma...

Reviews: