p. 11 / 39
User Alarms (UAx)
The user has the possibility to define a maximum of 8 programmable
alarms (UA1…UA8).
For each alarm, it is possible to define:
o
the
source
that is the condition that generates the alarm,
o
the
text
of the message that must appear on the screen when this
condition is met.
o
The
properties
of the alarm (just like for standard alarms), that is in
which way that alarms interacts with the power factor correction.
The condition that generates the alarm can be, for instance, the
overcoming of a threshold. In this case, the source will be one of the limit
thresholds LIMx.
If instead, the alarm must be displayed depending on the status of an
external digital input, then the source will be an INPx.
For every alarm, the user can define a free message that will appear on the
alarm page.
The properties of the user alarms can be defined in the same way as the
normal alarms. You can choose whether a certain alarm will disconnect the
steps, close the global alarm output, etc. See chapter
Alarm properties
.
When several alarms are active at the same time, they are displayed
sequentially, and their total number is shown on the status bar.
To reset one alarm that has been programmed with latch, use the
dedicated command in the commands menu.
For details on alarm programming and definition, refer to setup menu
M26Ошибка! Источник ссылки не найден.
Пользовательские аварийные сигналы (UAx)
Пользователь может определить не более 8 программируемых аварийных
сигналов (UA1…UA8).
Для каждого аварийного сигнала можно определить:
o
источник,
являющийся условием создания аварийного сигнала,
o
текст
сообщения, появляющегося на экране при выполнении
условия,
o
свойства
аварийного сигнала (подобные стандартным аварийным
сигналам), то есть то, как аварийные сигналы воздействуют на
коррекцию коэффициента мощности.
Например, условием, создающим аварийный сигнал, является превышение
порога. В этом случае источником будет один из пороговых пределов LIMx.
Если, наоборот, в зависимости от состояния внешнего цифрового входа,
требуется отобразить аварийный сигнал, то источником будет INPx.
Для каждого аварийного сигнала пользователь может определить
произвольное сообщение, которое будет показано на странице аварийных
сигналов.
Свойства пользовательских аварийных сигналов можно определить таким
же образом, как свойства обычных сигналов. Можно задать отключение
ступеней по определенным сигналам, глобальное закрытие выходов, и так
далее. См. раздел «
Свойства аварийных сигналов
».
При активации нескольких аварийных сигналов одновременно они
отображаются последовательно, и общее количество показывается в
строке состояния.
Чтобы сбросить один аварийный сигнал с запрограммированной
фиксацией, в меню команд имеется специальная команда.
Подробную информацию о программировании и определении аварийных
сигналов см. в меню настройки M26
Ошибка! Источник ссылки не найден.
Master-Slave configuration
To further extend the flexibility of use of DCRG8 it is available the Master-
Slave function, which allows, for plants with high installed power, to
compose a series of panels in cascade, each with its own controller and
associated capacitor banks.
This solution allows to expand in a modular way the power factor correction
system, in case it becomes necessary because of the increased needs of
the plant.
In this configuration, measurements are made only from the first controller
(Master) which controls a maximum of 32
logical
steps, that are then sent
to all the slave units.
The slave controllers drive their steps as indicated by the master, while
performing the ‘local’ protections like panel or capacitor overtemperature,
no-voltage release, harmonic protections etc.
The maximum possible configuration is one master with 8 slaves.
Example 1 (application in series):
It is required to create a system with 18 step of 40kvar each, divided into
three identical panels with 6 step (240kvar) each. For each panel, the 8 relay
outputs of the controller are used as follows: the first six for the steps (OUT1.
.6), the seventh for the cooling fan (OUT7) and the last for the alarm (OUT8).
On the master panel we will define 18 logical step of 50kvar. The steps from 1
to 6 will be 'mapped' on the outputs OUT1 .. 6 of the master, those from 7 to
12 on the outputs OUT1 .. 6 of slave1 and finally the steps from 13 to 18 on
the outputs OUT1 .. 6 of the slave 2. In this case, the parameter
P02.07
Smallest step power
will have to be set (on the master) to 40kvar.
Programming of the master:
PARAMETER
VALUE
DESCRIPTION
P02.07
40
40 kvar
P03.01.01
…
P03.18.01
1
All the 18 logic steps are 40kvar
P04.01.01…P04.06.01
Step 1…6
Outputs OUT1…OUT6 of the master are activated
by logical steps 1…6.
P04.07101
Fan
OUT7 of the master controls cooling fan
P04.08.01
All glb 1
OUT8 of the master controls global alarm 1
P05.01
COM1
COM port used for the link
P05.02
Master
Role of master
P05.03…P05.04
ON
Enables slave 1 and slave 2
P06.01.01…P06.06.01
Step 7…12
Outputs OUT1…OUT6 of slave 1 are activated by
logical steps 7…12.
P06.07.01
Fan
OUT7 of slave 1 controls cooling fan
P06.08.01
All glb 1
OUT8 of slave 1 controls global alarm 1
P07.01.01…P07.06.01
Step 13…18 Outputs OUT1…OUT6 of slave 2 are activated by
logical steps 13…18.
P07.07.01
Fan
OUT7 of slave 2 controls cooling fan
P07.08.01
All glb 1
OUT8 of slave 2 controls global alarm 1
Programming of slave 1:
P05.02
Slave1
Role: slave1
Конфигурация «Ведущее-подчиненное устройство»
Для обеспечения дополнительной универсальности DCRG8, доступна
функция «ведущее-подчиненное устройство». Благодаря ей на объектах с
высокой установленной мощностью можно объединять несколько приборов
в каскад, каждый со своим собственным регулятором и связанными
батареями конденсаторов.
Это решение позволяет добиться модульного расширения системы
корректировки коэффициента мощности по мере увеличения потребностей
установки.
В такой конфигурации измерения выполняет только первый регулятор
(ведущий), управляющий максимально 32
логическими
ступенями, которые
затем передаются всем подчиненным устройствам.
Ступени на подчиненных устройствах задаются ведущим прибором. При
этом подчиненные устройства обеспечивают «местную» защиту, например
от перегрева панели или конденсатора, от отсутствия напряжения,
гармонических искажений и т.д.
В максимально возможной конфигурации присутствует одно ведущее
устройство и 8 подчиненных.
Пример 1 (последовательное применение):
Необходимо создать систему с 18 ступенями по 40 квар каждая, с
разделением на три идентичные панели по 6 ступеней (240 квар).
Для
каждой панели 8 релейных выходов используются следующим образом:
первые шесть для ступеней (OUT1. .6), седьмой для вентилятора
охлаждения (OUT7) и последний для аварийного сигнала (OUT8).
На ведущей
панели задается 18 логических ступеней по 50 квар.
Ступени с 1 по 6
назначаются выходам OUT1 ..
6 ведущего устройства, ступени с 7 по 12 –
выходам OUT1 ..
6 подчиненного устройства 1 и, наконец, ступени с 13 по
18 присваиваются выходам OUT1 ..
6 подчиненного устройства 2.
В этом
случае параметру
P02.07 Smallest step power (Наименьшая мощность
ступени)
необходимо будет присвоить значение 40 квар (на ведущем
устройстве).
Программирование ведущего устройства:
ПАРАМЕТР
ЗНАЧЕНИЕ ОПИСАНИЕ
P02.07
40
40 квар
P03.01.01
…
P03.18.01
1
Все 18 логических ступеней по 40 квар
P04.01.01…P04.06.01
Step 1…6
Выходы OUT1…OUT6 ведущего устройства
активируются логическими ступенями 1…6.
P04.07101
Вентилятор OUT7 ведущего устройства управляет
вентилятором охлаждения
P04.08.01
All glb 1
OUT8 ведущего устройства управляет
глобальным аварийным сигналом 1
P05.01
COM1
COM-порт, используемый для связи
P05.02
Master
Роль ведущего устройства
P05.03…P05.04
ON
Включение подчиненного устройства 1 и
подчиненного устройства 2
P06.01.01…P06.06.01
Step 7…12
Выходы OUT1…OUT6 подчиненного
устройства 1 активируются логическими
ступенями 7…12.
P06.07.01
Fan
OUT7 подчиненного устройства 1 управляет
вентилятором охлаждения
P06.08.01
All glb 1
OUT8 подчиненного устройства 1 управляет
ЧП
«
Профиэлектро
»
Т
. +380 44 361-62-55, 80
e-mail: [email protected]
www. profielectro.net.ua