80070201-0302ffff
Sensor [SensorElementName] has transitioned to critical from a less severe state. (CPU 2
OverTemp)
Explanation:
This message is for the use case when an implementation has detected a Sensor transitioned to critical
from less severe.
May also be shown as 800702010302ffff or 0x800702010302ffff
Severity:
Error
Alert Category:
Critical - Temperature
Serviceable:
Yes
CIM Information: Prefix:
PLAT and
ID:
0522
SNMP Trap ID:
0
Automatically notify Support:
No
User response:
1.
Make sure that the fans are operating, that there are no obstructions to the airflow (front and rear of the server),
that the air baffles are in place and correctly installed, and that the server cover is installed and completely
closed.
2.
Check the ambient temperature. You must be operating within the specifications (see Features and specifications
for more information).
3.
Make sure that the heat sink for microprocessor n is installed correctly.
4.
(Trained technician only) Replace microprocessor n. (n = microprocessor number)
80070202-0701ffff
Sensor [SensorElementName] has transitioned to critical from a less severe state. (SysBrd Vol
Fault)
Explanation:
This message is for the use case when an implementation has detected a Sensor transitioned to critical
from less severe.
May also be shown as 800702020701ffff or 0x800702020701ffff
Severity:
Error
Alert Category:
Critical - Voltage
Serviceable:
Yes
CIM Information: Prefix:
PLAT and
ID:
0522
SNMP Trap ID:
1
Automatically notify Support:
No
User response:
1.
Check the system-event log.
2.
Check for an error LED on the system board.
3.
Replace any failing device.
4.
Check for a server firmware update. Important: Some cluster solutions require specific code levels or coordinated
code updates. If the device is part of a cluster solution, verify that the latest level of code is supported for the
cluster solution before you update the code.
5.
(Trained technician only) Replace the system board.
80070201-0302ffff • 80070202-0701ffff
Appendix A. Integrated management module II (IMM2) error messages
345
Summary of Contents for System x3650 M4 BD Type 5466
Page 1: ...System x3650 M4 BD Type 5466 Installation and Service Guide ...
Page 2: ......
Page 3: ...System x3650 M4 BD Type 5466 Installation and Service Guide ...
Page 8: ...vi System x3650 M4 BD Type 5466 Installation and Service Guide ...
Page 102: ...86 System x3650 M4 BD Type 5466 Installation and Service Guide ...
Page 130: ...114 System x3650 M4 BD Type 5466 Installation and Service Guide ...
Page 178: ...162 System x3650 M4 BD Type 5466 Installation and Service Guide ...
Page 189: ...v Type 2 SAS Figure 84 Cable routing Chapter 6 Removing and replacing components 173 ...
Page 606: ...590 System x3650 M4 BD Type 5466 Installation and Service Guide ...
Page 766: ...750 System x3650 M4 BD Type 5466 Installation and Service Guide ...
Page 775: ...Taiwan Class A compliance statement Notices 759 ...
Page 776: ...760 System x3650 M4 BD Type 5466 Installation and Service Guide ...
Page 778: ...762 System x3650 M4 BD Type 5466 Installation and Service Guide ...
Page 784: ...768 System x3650 M4 BD Type 5466 Installation and Service Guide ...
Page 785: ......
Page 786: ... Part Number 00KC029 Printed in USA 1P P N 00KC029 ...