80010204-1d07ffff
Numeric sensor [NumericSensorElementName] going low (lower critical) has asserted. (Fan 4
Tach)
Explanation:
This message is for the use case when an implementation has detected a Lower Critical sensor going
low has asserted.
May also be shown as 800102041d07ffff or 0x800102041d07ffff
Severity:
Error
Alert Category:
Critical - Fan Failure
Serviceable:
Yes
CIM Information: Prefix:
PLAT and
ID:
0480
SNMP Trap ID:
11
Automatically notify Support:
No
User response:
1.
Reseat the failing fan n, which is indicated by a lit LED near the fan connector on the system board.
2.
Replace the failing fan. (n = fan number)
80010204-1d08ffff
Numeric sensor [NumericSensorElementName] going low (lower critical) has asserted. (Fan 5
Tach)
Explanation:
This message is for the use case when an implementation has detected a Lower Critical sensor going
low has asserted.
May also be shown as 800102041d08ffff or 0x800102041d08ffff
Severity:
Error
Alert Category:
Critical - Fan Failure
Serviceable:
Yes
CIM Information: Prefix:
PLAT and
ID:
0480
SNMP Trap ID:
11
Automatically notify Support:
No
User response:
1.
Reseat the failing fan n, which is indicated by a lit LED near the fan connector on the system board.
2.
Replace the failing fan. (n = fan number)
80010701-0702ffff
Numeric sensor [NumericSensorElementName] going high (upper non-critical) has asserted.
(FHHL Amb Temp)
Explanation:
This message is for the use case when an implementation has detected an Upper Non-critical sensor
going high has asserted.
May also be shown as 800107010702ffff or 0x800107010702ffff
Severity:
Warning
Alert Category:
Warning - Temperature
Serviceable:
Yes
CIM Information: Prefix:
PLAT and
ID:
0490
SNMP Trap ID:
12
Automatically notify Support:
No
User response:
80010204-1d07ffff • 80010701-0702ffff
Appendix A. Integrated management module II (IMM2) error messages
323
Summary of Contents for System x3650 M4 BD Type 5466
Page 1: ...System x3650 M4 BD Type 5466 Installation and Service Guide ...
Page 2: ......
Page 3: ...System x3650 M4 BD Type 5466 Installation and Service Guide ...
Page 8: ...vi System x3650 M4 BD Type 5466 Installation and Service Guide ...
Page 102: ...86 System x3650 M4 BD Type 5466 Installation and Service Guide ...
Page 130: ...114 System x3650 M4 BD Type 5466 Installation and Service Guide ...
Page 178: ...162 System x3650 M4 BD Type 5466 Installation and Service Guide ...
Page 189: ...v Type 2 SAS Figure 84 Cable routing Chapter 6 Removing and replacing components 173 ...
Page 606: ...590 System x3650 M4 BD Type 5466 Installation and Service Guide ...
Page 766: ...750 System x3650 M4 BD Type 5466 Installation and Service Guide ...
Page 775: ...Taiwan Class A compliance statement Notices 759 ...
Page 776: ...760 System x3650 M4 BD Type 5466 Installation and Service Guide ...
Page 778: ...762 System x3650 M4 BD Type 5466 Installation and Service Guide ...
Page 784: ...768 System x3650 M4 BD Type 5466 Installation and Service Guide ...
Page 785: ......
Page 786: ... Part Number 00KC029 Printed in USA 1P P N 00KC029 ...