Table 5. DSA Preboot messages (continued)
v
Follow the suggested actions in the order in which they are listed in the Action column until the problem is solved.
v
See Chapter 4, “Parts listing, System x3200 M3 Types 7327 and 7328,” on page 133 to determine which components are
customer replaceable units (CRU) and which components are field replaceable units (FRU).
v
If an action step is preceded by “(Trained service technician only),” that step must be performed only by a Trained
service technician.
v
Go to the IBM support Web site at http://www.ibm.com/systems/support/ to check for technical information, hints, tips,
and new device drivers or to submit a request for information.
Message
number
Component
Test
State
Description
Action
201-803-xxx
Memory
Memory Test
Aborted
Test canceled:
could not enable
the processor
cache.
1. Turn off and restart the system.
2. Run the test again.
3. Make sure that the server firmware is
at the latest level. The installed
firmware level is shown in the DSA
event log in the Firmware/VPD
section for this component. For more
information, see “Updating the
firmware” on page 221.
4. Run the test again.
5. If the failure remains, go to the IBM
Web site for more troubleshooting
information at http://www.ibm.com/
systems/support/supportsite.wss/
docdisplay?brandind=5000008
&lndocid=SERV-CALL.
201-804-xxx
Memory
Memory Test
Aborted
Test canceled: the
memory controller
buffer request
failed.
1. Turn off and restart the system.
2. Run the test again.
3. Make sure that the server firmware is
at the latest level. The installed
firmware level is shown in the DSA
event log in the Firmware/VPD
section for this component. For more
information, see “Updating the
firmware” on page 221.
4. Run the test again.
5. If the failure remains, go to the IBM
Web site for more troubleshooting
information at http://www.ibm.com/
systems/support/supportsite.wss/
docdisplay?brandind=5000008
&lndocid=SERV-CALL.
201-805-xxx
Memory
Memory Test
Aborted
Test canceled: the
memory controller
display/alter write
operation was not
completed.
1. Turn off and restart the system.
2. Run the test again.
3. Make sure that the server firmware is
at the latest level. The installed
firmware level is shown in the DSA
event log in the Firmware/VPD
section for this component. For more
information, see “Updating the
firmware” on page 221.
4. Run the test again.
5. If the failure remains, go to the IBM
Web site for more troubleshooting
information at http://www.ibm.com/
systems/support/supportsite.wss/
docdisplay?brandind=5000008
&lndocid=SERV-CALL.
108
System x3200 M3 Types 7327 and 7328: Problem Determination and Service Guide
Summary of Contents for System x3200 M3
Page 1: ...System x3200 M3 Types 7327 and 7328 Problem Determination and Service Guide...
Page 2: ......
Page 3: ...System x3200 M3 Types 7327 and 7328 Problem Determination and Service Guide...
Page 20: ...xviii System x3200 M3 Types 7327 and 7328 Problem Determination and Service Guide...
Page 42: ...22 System x3200 M3 Types 7327 and 7328 Problem Determination and Service Guide...
Page 160: ...140 System x3200 M3 Types 7327 and 7328 Problem Determination and Service Guide...
Page 240: ...220 System x3200 M3 Types 7327 and 7328 Problem Determination and Service Guide...
Page 264: ...244 System x3200 M3 Types 7327 and 7328 Problem Determination and Service Guide...
Page 280: ...260 System x3200 M3 Types 7327 and 7328 Problem Determination and Service Guide...
Page 281: ......
Page 282: ...Part Number 90Y5683 Printed in USA 1P P N 90Y5683...