Table 18. LEDs on the secondary expander modules (continued)
LED
Color
Status
Description
Fault
2
Amber
On
Not used.
Blink
The secondary expander
module is being identified.
Off
Normal operation.
This task assumes that the following conditions were met:
• The expansion enclosure is slid out from the rack, as described in “Removing an expansion enclosure
from a rack: 2077-92F ” on page 79.
• The top cover was removed, as described in “Removing the top cover: 2077-92F ” on page 42.
Procedure
1. Identify the secondary expander module to be replaced; refer to Table 18 on page 90.
2. Press the release buttons on top of the secondary expander module to release the handles.
3. Rotate the handles outward to the unlocked position.
4. Lift the secondary expander module carefully out of the enclosure, as shown in Figure 93 on page 91.
Figure 93. Remove the secondary expander module
Important: To avoid electric shock after you remove the secondary expander module, do not touch
the connectors inside the enclosure (FRU P/N 01LJ112), which are shown in Figure 94 on page 92.
Chapter 2. Installing the system hardware 91