G8052R RackSwitch specification sheet
Hardware specifications provide detailed information for your IBM BNT RackSwitch, including
dimensions, electrical, power, temperature, environment, and service clearances.
Table 70. Dimensions
Height
Width
Depth
Weight (maximum)
44 mm (1.73 in.)
439 mm (17.3 in.)
445 mm (17.5 in.)
8.3 kg (18.3 lb)
Table 71. Electrical
Electrical characteristics
Properties
Power requirements
200 W
Voltage
90 - 264 V ac
Frequency
47 - 63 Hz
Maximum thermal output
682.4 Btu/hr
Phase
1
kVA
0.204
Table 72. Environmental and acoustical requirements
Environment/Acoustical
Operating
Storage
Airflow direction
Rear-to-front
Temperature, ambient operating
0°C - 40°C (32°F - 104°F)
Temperature, operating (fan failure) 0°C - 35°C (32°F - 95°F)
Temperature, storage
-40ºC to +85ºC (-40°F to 185°F)
Relative humidity range (non-
condensing)
10% - 90% RH
10% - 90% RH
Maximum altitude
3050 m (10000 ft)
12190 m (40000 ft)
Heat dissipation
444 Btu/hr
Acoustic noise
Less than 65 dB
G8124ER RackSwitch specification sheet
Hardware specifications provide detailed information for your IBM BNT RackSwitch, including
dimensions, electrical, power, temperature, environment, and service clearances.
Table 73. Dimensions
Height
Width
Depth
Weight (maximum)
44 mm (1.73 in.)
439 mm (17.3 in.)
381 mm (15.0 in.)
6.4 kg (14.1 lb)
Table 74. Electrical
Electrical characteristics
Properties
Power requirements
275 W
Voltage
100 - 240 V ac
Frequency
50 - 60 Hz
68 Power Systems: Site and hardware planning
Summary of Contents for 9008-22L
Page 1: ...Power Systems Site and hardware planning IBM...
Page 4: ...iv...
Page 14: ...xiv Power Systems Site and hardware planning...
Page 16: ...2 Power Systems Site and hardware planning...
Page 20: ...6 Power Systems Site and hardware planning...
Page 40: ...Figure 1 FC EPB8 power distribution panel 26 Power Systems Site and hardware planning...
Page 49: ...Figure 5 FC ERG0 rear rack extender top down view Site and hardware planning 35...
Page 123: ...Figure 35 Cable management bridge lances Site and hardware planning 109...
Page 163: ......
Page 164: ...IBM...