Figure 3. Caster and leveler locations
Note: Rack units are large and heavy and are not easily moved. As maintenance activities require access
at both the front and the back, extra room is needed. The footprint illustration does not show the radius of
the swinging doors on the I/O rack. A service clearance of 915 mm (36 in.) needs to be maintained on
front, rear, and sides of the I/O rack.
Related reference
7014-T00 and 7014-T42 rack weight distribution and floor loading
Racks can be heavy when populated with several drawers. Use the Weight distribution distances for racks
when loaded and Floor loading for racks when loaded tables to ensure proper floor loading and weight
distribution.
Related information
Planning for the installation of rear door heat exchangers
32 Power Systems: Site and hardware planning