![IBM 9008-22L Site And Hardware Planning Download Page 38](http://html1.mh-extra.com/html/ibm/9008-22l/9008-22l_site-and-hardware-planning_3427298038.webp)
Table 34. Dimensions for doors (continued)
Door model
Width
Height
Depth
Weight
Standard side
covers
10 mm (0.4 in.)
each
1740 mm (68.5 in.)
each
1042 mm (41.0 in.)
each
18 lbs 8.25 kg (18
lb) each
FC 6101 front door
(OEM)
639 mm (25.2 in.)
1740 mm (68.5 in.) 56 mm (2.3 in.)
14 kg (31 lb)
FC 6068 front door,
high perforation
639 mm (25.2 in.)
1740 mm (68.5 in.) 56 mm (2.3 in.)
14 kg (31 lb)
FC 6248 acoustic
doors, front and
rear
639 mm (25.2 in.)
each
1740 mm (76.6 in.)
each
198 mm (7.8 in.)
each
12.3 kg (27 lb)
each
Table 35. Electrical
1
Electrical characteristics
Properties
Power source loading maximum in kVA
2
8.4 (FC 6117
3
)
8.4 (FC EPB8
3,4
)
Notes:
1. The total rack power can be derived from the sum of the power that is used by the drawers in the
rack.
2. For FC EPB8, each side can support a maximum of 600 amps (A) and 10 circuit breakers. The PDP
can hold up to twenty (ten per power source) circuit breakers with ratings between 5 A and 90 A.
Each power source supports up to 8.4 kVA.
3. For more information about FC 6117 and FC EPB8, see “Model 7014-T00 rack with optional DC
power distribution panel” on page 25.
4. Preliminary data is subject to change.
See your individual server or hardware specifications for temperature and humidity requirements.
Rack noise levels depend on the number and type of drawers installed. See your server or hardware
specifications for specific requirements.
Note: All rack installations require careful site and facilities planning that are designed to both address
the cumulative drawer heat output and provide the airflow volume rates necessary to comply with drawer
temperature requirements. All rack installations require careful site and facilities planning that are
designed to address both the cumulative drawer heat output and provide the airflow volume rates
necessary to comply with drawer temperature requirements. Rack airflow requirements depend on the
number and type of drawers installed.
Note: Acoustic doors are available for IBM racks. Feature code 6248 is available for the 0551 and 7014-
T00 racks. Feature code 6249 is available for 7014-T42 racks. The overall sound reduction is
approximately 6 dB. The doors add approximately 381 mm (15 in.) to the depth of the racks.
Related reference
7014-T00 and 7014-T42 rack weight distribution and floor loading
24 Power Systems: Site and hardware planning
Summary of Contents for 9008-22L
Page 1: ...Power Systems Site and hardware planning IBM...
Page 4: ...iv...
Page 14: ...xiv Power Systems Site and hardware planning...
Page 16: ...2 Power Systems Site and hardware planning...
Page 20: ...6 Power Systems Site and hardware planning...
Page 40: ...Figure 1 FC EPB8 power distribution panel 26 Power Systems Site and hardware planning...
Page 49: ...Figure 5 FC ERG0 rear rack extender top down view Site and hardware planning 35...
Page 123: ...Figure 35 Cable management bridge lances Site and hardware planning 109...
Page 163: ......
Page 164: ...IBM...