Debounce time (µs)
Here, you can define the debounce time in µs
Active
Enabling/disabling the signal
10.2.7
ibaPQU-S
– “Status” tab
Figure 18: ibaPQU-S module
– “Status” tab
In the Status tab, you can enable status signals:
Signal
Meaning
UDP data loss […]
Data packet lost (per measurement interval)
Data correct […]
All data transmitted correctly (for different
measurement intervals)
PLL
unlocked […]
Synchronization with reference signal failed (for
different measurement intervals)
ADC error […]
Central unit does not receive data from the input
module (for different measurement intervals)
Calculation error […]
Calculation error (in different measurement
intervals)
Calculation period incomplete […]
Calculation does not comprise the entire
measurement interval (for different measurement
intervals)