background image

                                                                                      4.0 General Description 

 

12                                                                                                                                                        CC1132751C 

4.3 Compressor Assembly (Fig.4.2) 

The unit comprises of a single stage, oil flooded, rotary, sliding 
vane compressor driven by an electric motor mounted to a base. 
It is supplied with control panel, starter, and oil cooler/air 
aftercooler with all accessories piped in and electrically 
connected. 

The intake cover (A) is assembled directly to the compressor (B) 
which is fitted to the motor flange (C). A flexible coupling drives 
the compressor rotor from the motor drive shaft, enclosed inside 
the bell housing (D). The motor is bolted to the vertical column 
supported by the base. 

An electrically driven, impellor type, horizontally mounted fan (E) 
is located below the combination oil cooler/air aftercooler matrix 
(F). This draws cooling air through the air filter (G) and forces it 
through the cooler matrix. 

The electronic controller (H) with an LCD screen is mounted in 
the starter (J). An emergency stop button (K) is located on the 
front controller panel. 

For RS models, the inverter drive (L) is mounted inside the 
starter compartment, behind the starter panel door (J). 

The compressor air intake is protected by an air intake filter (M), 
and the oil system is filtered by an oil filter (N). An oil level sight 
glass (O) is mounted adjacent to the oil filter. 

The compressor is filled and topped up with oil via the oil filler 
(P). The sight glass (O) will be full when oil overflows from the 
level plug orifice (Q). 

Oil is drained from the compressor and cooler  by removing the 
drain plug (R). 

The compressor pressure gauge (S) is visible when the front 
panel is open. 

Oil separator (T) located on the compressor separator manifold 
ensure air delivered through the minimum pressure valve has a 
cleanliness of less than 3 ppm (parts per million by weight). 

Air is delivered through the air delivery pipe (U) to the after 
cooler (F) before discharge from the unit. 

 

The oil supply to the cooler is through oil feed pipe (V) with the 
cool oil return through oil return pipe (W) For a quick warm up, a 
thermal by-pass valve (Y) allows the oil supply to by-pass the 
cooler on initial start up. 

4.4 Electronic Controller 

Controllers have menu structures that contain all the parameters 
and settings for safe operation of the compressor. 

a) 

[MAINTENANCE SCHED] 

b) 

[CONTROL MENU] 

c) 

[FAULT MEMORY] 

d) 

[TIMER CONTROL] 

e) 

[LIMIT VALUES] 

f) 

[OPTIONAL IN/OUTPUTS] 

All  menus  are available to view, the [MAINTENANCE SCHED] 
and [LIMIT VALUES] are reserved for fully trained personnel and 
require a service or master code for entry. 

Further explanation on menu structures is given in the following 
sections, 5.0 Operating Instructions and 6.0 Adjustments. 

 

 
 

Fig 4.2 Compressor Assembly 


 

 

 

 

 
 


 

 

 
 

P     O     Q     M 
 
 

J     K     U 
 
 


 

 

 

 

 

 

 
 


 
 

Summary of Contents for HR04

Page 1: ...HR04 HR07 Models User Handbook Original Instructions CC1132751D 10 2018 GB...

Page 2: ......

Page 3: ...3 Compressor Assembly Fig 4 2 12 4 4 Electronic Controller 12 5 0 Operating Instructions 13 5 1 Checking Procedure Before Starting 13 5 2 Operator Control Keys Fig 5 1 13 5 3 Status Display Lights 13...

Page 4: ...17 7 8 Oil Separator Fig 7 1 17 7 9 Oil Cooler Aftercooler Fig 7 2 18 7 10 Cabinet Air Filter Fig 7 2 18 7 11 Electric Motor 18 7 12 Electrical Connections 18 7 13 Service Schedule 18 8 0 Controller...

Page 5: ...odel HR04ER07 4035S000 50Hz model HR04ED07 4035S000 50Hz model HR04ERD07 4035S000 50Hz model HR04E07 5736D005 60Hz model HR04E10 2036D005 60Hz model HR04E10 4035S000 50Hz model HR04ER10 4035S000 50Hz...

Page 6: ...Warning unit is remotely controlled and may start without warning Read the instruction manual Do not operate the machine the machine without the guard being fitted Warning do not start the machine wi...

Page 7: ...ed over a period of time may cause problems that affect the performance and reliability of this compressor Problems may occur when compressors run for short periods on low air demand where they don t...

Page 8: ...ETTINGS Nominal Pressure bar psi 7 0 or 10 0 102 or 145 7 0 102 Minimum Pressure Valve bar psi 5 5 to 6 0 80 to 87 Load Cut in Pressure bar psi 6 5 or 9 5 94 or 138 7 0 102 Unload Cut out Pressure bar...

Page 9: ...low of the compressor Total resistance of the system must not exceed 50 mbar If resistance is expected to be greater fan assistance will be required 3 4 Electrical Connections WARNING CONNECTION TO OR...

Page 10: ...otation is correct by observing pressure rise on the compressor gauge Cooling fan operation is clockwise all RS units have automatic stop start cooling fans that cut in at 85 C 185 F operating tempera...

Page 11: ...ir demands The compressor will load unload and stop start automatically in response to air demand Motor restarts are set to 10 times per hour for single speed units and 30 times for RS units Run on ti...

Page 12: ...d adjacent to the oil filter The compressor is filled and topped up with oil via the oil filler P The sight glass O will be full when oil overflows from the level plug orifice Q Oil is drained from th...

Page 13: ...ssure are viewed here The third row shows status fault and warning messages The HYDROVANE Pro is fitted with two light signals green red Flashing system is ready the motor may start up automatically a...

Page 14: ...sure set point the REVS Reduced Energy Venting System sequence will begin If there is an air demand during the REVS run on time sequence the compressor returns to full load operation If there is no ai...

Page 15: ...IN POINT or p2 TARGET PRESSURE RS e RUN ON TIME f AUTOMATIC OPERATION g ENABLE REMOTE START h TIMER CONTROL i p2 TIMER CONTROL j AUTO RESTART k POWER LOSS TIME l START UP DELAY m DRYER PRE RUN n RS48...

Page 16: ...this is the basis for accurate timer operations Go to the TIMER CONTROL sub menu use the or key to select from seven different timer units The status line of each switching unit is as follows a b c d...

Page 17: ...SAFETY NOTICE ADVISING THAT WORK IS BEING CARRIED OUT ON THE COMPRESSOR CLOSE THE AIR OUTLET VALVE TO ISOLATE THE COMPRESSOR FROM THE AIRLINE SYSTEM FIT A SAFETY NOTICE ADVISING THAT IT IS NOT TO BE...

Page 18: ...special attention to power connections cables connected to contactors and incoming terminals and ensure all earthing wiring is present and undamaged Close the starter panel door and lock with the key...

Page 19: ...d X X X X Check motor conduit cables secure X X X X Check motor for damage X Check motor starter for loose connections X X X X Check motor for vibration X X X X Check flexible control pipes X X X Chec...

Page 20: ...motor for damage X Check motor starter for loose connections X X X Check motor for vibration X X X Check flexible control pipes X X Check oil seal for leakage X X Check drive media key X Check starte...

Page 21: ...t now starts automatically after a previously set time f WARNING START IN Alternating with AFTER DRYER PRE RUN The unit has been switched on and is ready The unit starts automatically after the dryer...

Page 22: ...he Engineering Department Gardner Denver Ltd Web www hydrovaneproducts com www gardnerdenver com E mail sales compair com hydrovane nfo uk gardnerdenver com CC1132751D hydrovane USA 1301 North Euclid...

Page 23: ......

Page 24: ...ons for hydrovane Various Applications Global Expertise Gardner Denver Ltd Claybrook Drive Redditc h Worc estershire B98 ODS UK T 44 0 1527 525522 838200 E hydrovane info uk gardnerdenver com www hydr...

Reviews: