Attention:
Electrical connection and commissioning shall only be executed by an authorised expert
according to VDE regulations!
Attention:
Protect your eyes and skin against UV light. UV light is causing strong sunburn and painful
conjunctivitis.
Activate UV lamp only after it has been already inserted into the reactor, never before!
A safe operation of system is ensured through indication of the UV intensity. If the UV intensity is
falling below 50% during operation, maintenance and if necessary a replacement of UV lamp must be
performed. The disinfection effect is not any longer ensured.
Attention:
After replacing the UV lamp an adjustment/tuning of the end value as well as a reset of
operating hours must be executed.
2. Taking out of service
The UV lamp is exposed to an intense temperature during operation. To prevent any excessive
overheating of system parts, and any harm to the operator, the system must be turned off electrically
by the On/Off power switch and left turned off for some time before any works can commence. For
general protection of system and personal safety the system must be disconnected from the mains
supply.
The system must be now shut off hydraulically. Open the water bypass if present, then close inlet and
outlet valves.
The housing can be now completely drained of the water by means of the drain tap.
Maintenance and cleaning shall be performed prior to the system being put into operation again (see
Chapter V).
Summary of Contents for HYDROWELL Compact 10E
Page 16: ...P a g e 16 38 Reactor Dimensional drawing with parameters from technical data sheet...
Page 18: ...P a g e 18 38 Control Box Power switch ON OFF UV monitor Cable fittings...
Page 30: ...P a g e 30 38 Appendices 1 Installation Schematic UV Disinfection System...
Page 31: ...P a g e 31 38 Appendices 2 Wiring diagram HydroWELL 2 E 5 E and 10 E with sensor...