2. Technical faults
A technical fault is displayed through a red warning light. The system shuts down and the operating
hours counter (relative hours) stops. Furthermore, the potential-free output as well as the optional
solenoid valve is switched to the free use by the operator.
Malfunctions and other interruptions in operation are detected by the UV sensor and in case of the
intensity falling below 60% they are triggered. If the intensity is reaching 70% again the fault signal
gets inactivated and the system re-starts operation.
Possible failure reasons
Trouble-shooting
Contamination of quartz tube insert
Clean; remove deposits
Contamination of UV sensor
Clean; remove deposits
Malfunction of UV sensor
Replace UV sensor
Prematurely ageing or malfunction of UV lamp
Replace UV lamp
Accumulation of air in area of UV sensor
Let the system ventilate
Too strong turbidity of water (e.g. by means of
faulty pre-treatment)
Ensure sufficient water quality with high UV
transmission
Additionally, a failure of electrical parts can appear too in the control unit box. Such damages may for
example occur in case of overvoltage.
Possible failure reasons
Trouble-shooting
Malfunction of electronic ballast
Replace electronic ballast
Fuse blown
Replace fuse
Other damages on electronic parts
Investigation/Replacement by authorised expert
Attention:
Electrical works must only be executed by authorised experts according to VDE
regulations!
For queries regarding operation and handling of UV disinfection system, please contact our
service department:
Hydrotec (UK) Ltd
Hydrotec House
Manor Courtyard, Hughenden Avenue
High Wycombe, Bucks HP13 5RE
Tel: 01494 796 040
Email: [email protected]
Summary of Contents for HYDROWELL Compact 10E
Page 16: ...P a g e 16 38 Reactor Dimensional drawing with parameters from technical data sheet...
Page 18: ...P a g e 18 38 Control Box Power switch ON OFF UV monitor Cable fittings...
Page 30: ...P a g e 30 38 Appendices 1 Installation Schematic UV Disinfection System...
Page 31: ...P a g e 31 38 Appendices 2 Wiring diagram HydroWELL 2 E 5 E and 10 E with sensor...