Brine line
The brine is taken from the brine tank by means of a hose.
Brine is drawn in by the control valve and flows through the
intake pipe to the injector, passing the injector, before
reaching the filter media. The injector is used to limit the
brine quantity that is dependent on the quantity of filter
media.
The brine intake hose has to be fixed to the hose connection
of the brine valve (in brine tank). The hose must be fixed to
the connections of the control valve.
HYDRO
ION
®
VAS - CS 1
Cont
rol valve 1“:
connection 3/8“
HYDRO
ION
®
VAS - CS 1.5
Control valve 1.
5”:
connection 1/2“
HYDRO
ION
®
VAS - CS 2
Cont
rol valve 2“:
connection 3/4“
The waste water hose that is included in the delivery scope
must be connected in an appropriate length and size to the
local drain.
Brine lack sensor
The brine lack sensor is mounted already in the brine tube of
the brine tank and has to be connected electrically to the
micro processor control.
Chlorinator
If necessary and ordered, the
chlorinator is already
mounted in the brine intake
pipe.
Waste water connection
Waste water connection of control
valve 1“:
3/4“
Waste water connection
of control valve 1 1/2“:
3/4“ or 1“
Waste water connection o
f control valve 2“:
1“
The waste water hose must be fixed in an appropriate length
to the connection leading into drain.
It must be guaranteed that discharge of waste water into the
local drain (channel) is without any pressure applied.
Otherwise, regeneration takes place whereby no brine is
drawn in.
To control valve
From brine tank
fig.21