2-8
E
lEctrIcal
/ c
ontrollEr
/ W
atEr
/ r
EfrIgEratIon
P/N 3053328_C
U.S. & Canada 1-800-922-1919 • Mexico 1-800-890-2900 • WWW.HUSSMANN.COM
Input No.
Type of Input
Description
1
Supply
Reference "-"/GND (24Vac or 24Vdc)
2
Pb1
Config analog input (NTC, PTC, 0 - 20mA, 4 - 20mA, 0 - 10V, 0 - 1V, 0 - 5V, DI, CPC, CPC High)
3
Pb2
Config analog input (NTC, PTC, 0 - 20mA, 4 - 20mA, 0 - 10V, 0 - 1V, 0 - 5V, DI, CPC, CPC High)
4
Pb3
Config analog input (NTC, PTC, 0 - 20mA, 4 - 20mA, 0 - 10V, 0 - 1V, 0 - 5V, DI, CPC, CPC High)
5
(+12V)
Additional power +12Vdc
6
(+5V)
Additional power +5Vdc
7
Out1
Analogue output (0 - 10V, 4 - 20mA, Relay)
8
Out2
Analogue output (0 - 10V, 4 - 20mA, Relay)
9
Supply
Reference "+" power supply (24Vac or 24Vdc)
10
Pb4
Config analog input (NTC, PTC, 0 - 20mA, 4 - 20mA, 0 - 10V, 0 - 1V, 0 - 5V, DI, CPC, CPC High)
11
Pb5
Config analog input (NTC, PTC, 0 - 20mA, 4 - 20mA, 0 - 10V, 0 - 1V, 0 - 5V, DI, CPC, CPC High)
12
Pb6
Config analog input (NTC, PTC, 0 - 20mA, 4 - 20mA, 0 - 10V, 0 - 1V, 0 - 5V, DI, CPC, CPC High)
13
PbC
Common analogue inputs (NTC, PTC, DI, CPC, CPC High)
14
GND(-)
Additional power reference 5Vdc and 12Vdc, analogue inputs (0 - 20mA, 4 - 20mA, 0 - 10V, 0 -
1V, 0 - 5V), analogue outputs. Note: Pressure sensors GND reference terminate
15
Out3
Analogue output (0 - 10V, 4 - 20mA, Relay)
16
Out4
Analogue output (0 - 10V, 4 - 20mA, Relay)
Connector for 24Vac/dc power supply
Analogue inputs (Pb1 - Pb6), Pbc)
Additional Power (+5Vdc, +12Vdc, GND)
Analogue outputs (Out1 - Out4, GND)
24Vac/dc digital inputs (DI1 - DI11, GND)
Note: Not a dry contact switch, power supply 24Vac or 24Vdc required to activate switch
If using 24Vdc, pin 31 is GND
20
DI1
Digital input 24Vac/dc
21
DI2
Digital input 24Vac/dc
22
DI3
Digital input 24Vac/dc
23
DI4
Digital input 24Vac/dc
24
DI5
Digital input 24Vac/dc
25
DI6
Digital input 24Vac/dc
26
DI7
Digital input 24Vac/dc
27
DI8
Digital input 24Vac/dc
28
DI9
Digital input 24Vac/dc
29
DI10
Digital input 24Vac/dc
30
DI11
Digital input 24Vac/dc
31
GND(-)
Reference "-" for digital inputs from 1 to 11 (Note: Dry Contacts N/A, Source Required)
40
C
Common relays 1,2,3 and 4 (MAX 10A)
41
C
Common relays 1,2,3 and 4 (MAX 10A)
42
RL1
Relay normally open contact
43
RL2
Relay normally open contact
44
RL3
Relay normally open contact
45
RL4
Relay normally open contact
46
RL5
Relay normally open contact
47
C
Common relays 1,2,3 and 4 (MAX 10A)
48
C
Common relays 1,2,3 and 4 (MAX 10A)
49
RL6
Relay normally open contact
50
RL7
Relay normally open contact
51
RL8
Relay normally open contact
Digital relay outputs
4 NO relays, 2 common
Note: Pin 40,41 common to pins 42,43,44,45
Common
Digital relay outputs
4 NO relays, 2 common
Note: Pin 47,48 common to pins 46,49,50,51