CoreLink
™
Case Controller
U.S. & Canada 1-800-922-1919 • Mexico 1-800-890-2900 • WWW.HUSSMANN.COM
5.13
Fan setting, C8: Fans:
Page#1
•
Navigate to C8: Fans setpoints to verify following 6 read/write parameters
E2 Parameter
CoreLink Parameter
Description
Range
FanCtrlMode
Fan Mode
4 selectable fan control modes.
0, "OnRef-
OfDef", 1,
"OnCnt-
OfDef", 2,
"OnRef-
OnDef", 3,
"OnCnt-OnDef"
FanAfterDefrost
Fan Operation after Defrost
Not Used:
By temperature:
In refrigeration mode if
selected termination temperature sensor is above
the fan setpoint, the fan output is OFF.
By time:
After defrost and switching into
refrigeration mode, the fan starts the delay timer
for a user-defined time before the output is
active.
2, "Time", 1,
"Temperature"
, 0, "NU"
FanSetpoint
Fan Setpoint
Temperature setpoint in which case fans will
start. (Temperature Mode)
(-10 to 70) °F
FanHys
Fan Hysteresis
Temperature margin from the fan setpoint in
which the fan will not be active.
(1 to 30)
FanTimeDelay
Fan Delay
After defrost and switching into refrigeration
mode, time before fans start. (Time Mode)
(0 to 30)x 10
sec
Fan_Dual_Temp