CoreLink
TM
P/N 3128012_A
27
CoreLink
™
Case Controller
U.S. & Canada 1-800-922-1919 • Mexico 1-800-890-2900 • WWW.HUSSMANN.COM
5.7
Defrost configuration setting, C7: Defrost
•
Navigate to C7 for the Defrost SETUP
•
Verify the E2 settings for Defrost Parameters, Defrost Durations, Input Selection, and
Defrost Mode of E2 parameter versus CoreLink parameters list to be verified.
E2 Parameter
CoreLink Parameter
Description
Range
DefrType
Defrost Mode
Electric mode for cases with installed electric
heaters. Hot gas mode for cases with hot gas
defrosts system.
3, "Elec Def -
Indiv Coils", 2,
"Modular
Defrost", 1, "Hot
Gas", 0, "Electric",
4, "Off Time"
DefrDuration
Max Defrost Duration
Maximum time in minutes for active defrost
mode. Prevents continuous defrost due to faulty
termination temperature sensor failing to
terminate cycle.
(1 to 60) min
DefrDelay
Defrost Delay
After switching from refrigeration to defrost, the
delay until defrost starts.
(0 to 30) min
TermTempSelect
Termination Temperature
Sensor
Use analog input coil out
[BLUE]
temperature
sensor or analog input defrost
[ORANGE]
temperature termination sensor.
1, "Coil Out
Temp", 0, "Defr
Term Temp"
TermTempComb
Temperature Combination
Maximum:
Uses the highest value between all
available/enabled coil-out temperature sensors
or defrost-termination sensors.
Minimum:
Uses the lowest value between all
available/enabled coil-out temperature sensors
or defrost-termination sensors.
Average:
Uses the average value between all
available/enabled coil-out temperature sensors
or defrost-termination sensors.
2, "Min", 1,
"Max", 0, "Avg"
TermSetpoint
Termination Temperature
Setpoint
Temperature setpoint at which defrost ends.
(0 to 99) °F
DripTime
Drip Time
Amount of time after defrost for the coil to drip. (0 to 30) min
MaxWait
Max Wait
Refrigeration starts if in wait period and the end-
wait input is active. If no supervisory controller is
available (offline), the application ignores the
end wait-input and will not use it for the start
refrigeration logic.
(1 to 60) min
DefrFreq
Defrost Interval
Time between defrost cycles in hours.
(1 to 255) hours
TermType
Defrost Termination Mode
Use termination temperature sensor or
digital/network input.
1, "Digital", 0,
"Temp"
DefrMin
Min Defrost Duration
Minimum time in minutes for active defrost
mode. Prevents early defrost termination due to
faulty termination temperature sensor.
(1 to 40) min