CoreLink
™
Case Controller
U.S. & Canada 1-800-922-1919 • Mexico 1-800-890-2900 • WWW.HUSSMANN.COM
5.15
Antisweat config, C5: Antisweat:
•
Navigate to C5: Antisweat to verify 4 read/write parameters including Dew setpoints
Max min output of Antisweat heater output , check range as well.
E2 Parameter CoreLink Parameter
Description
Range
DewSet
Dew Setpoint
If no network dewpoint value is available, the
frame temperature maintains a user-adjusted
band above the dewpoint setpoint.
(0 to 100) °F
DewPB
Dew Proportional Band
User defined range from which the temperature
can drift from the Dew Setpoint.
(0 to 20) °F
ASWMax
Max Output
Maximum anti-sweat power output.
(0 to 100) %
ASWMin
Min Output
Minimum anti-sweat power output.
(0 to 100) %