CoreLink
TM
28
P/N 3128012_A
U.S. & Canada 1-800-922-1919 • Mexico 1-800-890-2900 • WWW.HUSSMANN.COM
5.7.1
How to Schedule A Defrost in connected CoreLink
Using E2 Standard Circuit
•
Start with an E2 that has a Standard Circuit application added
•
Setup Standard Circuit defrost schedule (tabs C5, C6)
•
Navigate to CoreLink (Press Menu, F8 and select 1)
•
Enter Setup mode F5
•
Navigate to Inputs-NET tab (C6)
•
Point the CoreLink’s DEFROSTINIT_NET parameter to E2: Standard Circuit name: Defrost