CoreLink
TM
26
P/N 3128012_A
U.S. & Canada 1-800-922-1919 • Mexico 1-800-890-2900 • WWW.HUSSMANN.COM
•
Refrigeration setpoints of E2 parameter versus CoreLink parameters list to be verified.
Check the following 28 Read/Write & 3 Write parameters.
E2 Parameter
CoreLink Parameter
Description
Range
SETPOINT1
Temp Setpoint 1
Case Temp Setpoint 1
(-40 to 90) °F
DB
Deadband
Deadband
(1 to 45) °F
SETPOINT2
Temp Setpoint 2
Case Temp Setpoint 2
(-40 to 90) °F
Control_Mode
Control Mode
Control Type Strategy
0, "Standard", 1,
"Continuous", 2,
"Suction", 3, "SH
Only"
SETPOINT3
Temp Setpoint 3
Case Temp Setpoint 3
(-40 to 90) °F
TempPB
P
Proportional Band
(1 to 30) °F
TempRS
Band Offset
Band Offset
(-50 to 50) °F
TempINC
I
Integral ( 0 to 255 sec )
(0 to 255 sec)
TempDER
D
Derivative Sampling Time (0 to 255 sec)
(0 to 255 sec)
TempDDER
Derivative Time
Derivative Time
(0 to 255 sec)
DrAct
Door Switch Active
Door Switch Active
1, "Yes", 0, "No"
DrRefOn
Door Alarm Timer
Door Refrigeration Timer
(0 to 120)x 10 sec
DrAlrm
Door Alarm Delay
Door Alarm Active Delay
(0 to 120)x 10 sec
CswAct
Clean Switch Active
Clean Switch Active
1, "Yes", 0, "No"
CswRefOn
Clean Alarm Delay
Clean Switch-Refrigeration ON Delay
(0 to 360)x 10 sec
CTMode
Control Temp Mode
Control Mode
4, "Individual",
3, "Mix", 2,
"Average", 1,
"Minimum", 0,
"Maximum"
Weight1
Weight1
Discharge 1 weight, (0~100)
0-100%
Weight2
Weight2
Discharge 2 weight, (0~100)
0-100%
Weight3
Weight3
Discharge 3 weight, (0~100)
0-100%
ControlMix
Control Mix
Control Mix
2, "Coil3", 1,
"Coil2", 0,
"Coil1"
DoorMode
Door Mode
Door Mode
0, "Alarm", 1,
"Shutdown"
CleanMode
Clean Mode
Clean Mode
1, "BackOn", 0,
"Normal"