CoreLink
TM
32
P/N 3128012_A
U.S. & Canada 1-800-922-1919 • Mexico 1-800-890-2900 • WWW.HUSSMANN.COM
Valve Parameters setpoints of E2 parameter versus CoreLink
•
Navigate to C0: More, then to Valve Parameters to verify 21 Read Write parameters as
below
E2 Parameter
CoreLink
Parameter
Description
Range
VALVETYP1
Valve Type 1
Predefined valve selection for valve
one. This will overwrite valve
parameters with the controller
defaults for the selected valve. Use
manual for custom applications.
13, "SporlSEH(I)175", 12, "SporlSEH(I)100", 11, "SporlSEI50",
10, "SporlSER(I)GJK", 9, "SporlSEI30", 8, "SporlSER1.5to20", 7,
"SporlSEI.5to11", 6, "DanfETS-250/400", 5, "DanfETS-100", 4,
"DanfETS-25/50", 3, "AlcoEX8-500st/s", 2, "AlcoEX7", 1,
"AlcoEX4-5-6", 0, "Manual"
VALVETYP2
Valve Type 2
Predefined valve selection for valve
two. This will overwrite valve
parameters with the controller
defaults for the selected valve. Use
manual for custom applications.
13, "SporlSEH(I)175", 12, "SporlSEH(I)100", 11, "SporlSEI50",
10, "SporlSER(I)GJK", 9, "SporlSEI30", 8, "SporlSER1.5to20", 7,
"SporlSEI.5to11", 6, "DanfETS-250/400", 5, "DanfETS-100", 4,
"DanfETS-25/50", 3, "AlcoEX8-500st/s", 2, "AlcoEX7", 1,
"AlcoEX4-5-6", 0, "Manual"
VALVETYP3
Valve Type 3
Predefined valve selection for valve
three. This will overwrite valve
parameters with the controller
defaults for the selected valve. Use
manual for custom applications.
13, "SporlSEH(I)175", 12, "SporlSEH(I)100", 11, "SporlSEI50",
10, "SporlSER(I)GJK", 9, "SporlSEI30", 8, "SporlSER1.5to20", 7,
"SporlSEI.5to11", 6, "DanfETS-250/400", 5, "DanfETS-100", 4,
"DanfETS-25/50", 3, "AlcoEX8-500st/s", 2, "AlcoEX7", 1,
"AlcoEX4-5-6", 0, "Manual"
MINSTEPS_V1
Min Steps 1
Below this number of steps, valve
one has to be considered closed. In
case of alarms or no consensus from
the thermostat, the valve moves to
this number of steps. This is the
valve manufacturer recommended
lower valve opening limit.
(0 to 50)x 10 Steps
MINSTEPS_V2
Min Steps 2
Below this number of steps, valve
two has to be considered closed. In
case of alarms or no consensus from
the thermostat, the valve moves to
this number of steps. This is the
valve manufacturer recommended
lower valve opening limit.
(0 to 50)x 10 Steps
MINSTEPS_V3
Min Steps 3
Below this number of steps, valve
three has to be considered closed. In
case of alarms or no consensus from
the thermostat, the valve moves to
this number of steps. This is the
valve manufacturer recommended
lower valve opening limit.
(0 to 50)x 10 Steps
MAXSTEPS_V1
Max Steps 1
Above this number of steps, valve
one has to be considered open. This
is the valve manufacturer
recommended higher valve opening
limit.
(0 to 800)x 10 steps
MAXSTEPS_V2
Max Steps 2
Above this number of steps, valve
two has to be considered open. This
is the valve manufacturer
recommended higher valve opening
limit.
(0 to 800)x 10 steps
MAXSTEPS_V3
Max Steps 3
Above this number of steps, valve
three has to be considered open.
This is the valve manufacturer
recommended higher valve opening
limit.
(0 to 800)x 10 steps
INITSTEPS_V1
Initial Step
Regulation 1
When the valve regulation starts,
valve one moves to this position. As
soon as the valve is in position the
compressor can start.
(0 to 800)x 10 steps
INITSTEPS_V2
Initial Step
Regulation 2
When the valve regulation starts,
valve two moves to this position. As
soon as the valve is in position the
compressor can start.
(0 to 800)x 10 steps
INITSTEPS_V3
Initial Step
Regulation 3
When the valve regulation starts,
valve three moves to this position.
As soon as the valve is in position the
compressor can start.
(0 to 800)x 10 steps
EXTRASTEPS_V1
Extra Step 1
When valve one is at its min number
of step (From Min Steps), the valve
adds this many extra close steps to
recover possible lost steps. Valve
Overrun.
(0 to 500) steps
EXTRASTEPS_V2
Extra Step 2
When valve two is at its min number
of step (From Min Steps), the valve
adds this many extra close steps to
recover possible lost steps. Valve
Overrun.
(0 to 500) steps
EXTRASTEPS_V3
Extra Step 3
When valve three is at its min
number of step (From Min Steps),
the valve adds this many extra close
steps to recover possible lost steps.
Valve Overrun.
(0 to 500) steps
RELAXSTEPS_V1
Relax Step 1
After any extra steps, if any, valve
one is forced open for the number of
steps specified here.
(0 to 500) steps
RELAXSTEPS_V2
Relax Step 2
After any extra steps, if any, valve
two is forced open for the number of
steps specified here.
(0 to 500) steps
RELAXSTEPS_V3
Relax Step 3
After any extra steps, if any, valve
three is forced open for the number
of steps specified here.
(0 to 500) steps
PEAKCURR_1
PEAKCURR_2
PEAKCURR_3